parameter
F. scale sensor
p = XX.X [bar]
Min value sensor
p = XX.X [bar]
Max alarm value
p = XX.X [bar]
Min alarm value
p = XX.X [bar]
Ext.set enabling
ON/OFF
Set value
p = XX.X [bar]
Compensation
p = XX.X [bar]
Set value 2
p = XX.X [bar]
Compensation 2
p = XX.X [bar]
Set value update
t = XX [s]
desciption
Sensor full scale.
16
Sensor minimum value.
0
Maximum value allowed in the system.
If the readen value goes over this value,
an alarm occurs and the pump is
10
stopped. Pump is automatically
restarted if the readen value goes below
the maximum value for a period of at
least 5 seconds.
Minimum value allowed in the system. If
the readen value goes lower than this
value, an alarm occurs and the pump is
0
stopped. Pump is automatically
restarted if the readen value goes
higher than the minimum value for a
period of at least 5 seconds.
Enabling of set value changing by analog
input AN3.
OFF
The set value to be kept constant.
3
Value compensation at the maximum
frequency for each pump. Acting on the
0
green button you can reverse the sign.
The set value to be kept constant.
3
Value compensation at the maximum
frequency for each pump. Acting on the
0
green button you can reverse the sign.
Time to update set value for
compensation.
5
    
    
    
    