Huawei DBS3900 Installation Manual page 39

Lampsite
Hide thumbs Also See for DBS3900:
Table of Contents

Advertisement

DBS3900 LampSite
Installation Guide
l
l
l
l
l
l
l
International Standards
l
l
l
l
l
l
l
Bending radius
l
l
l
Cable Binding
l
l
l
l
l
l
Safety
Issue 06 (2015-10-30)
Code for Engineering Design of Generic Cabling System for Building and Campus (GB
50311-2007)
Code for Engineering Acceptance of Generic Cabling System for Building and Campus
(GB50312-2007).
Security Protection Engineering Technology Specifications (GB 50348-2004)
Code for Construction and Acceptance of the Electronic Information System Room (GB
50462-2008)
Code for Quality Acceptance of the Intelligent Building Engineering (GB 50339-2003)
Code for Quality Acceptance of Electric Engineering Construction in Building (GB
50303-2002)
Technical Specification for Construction and Acceptance of Telecommunication Conduit
Engineering (GB 50374-2006)
Generic Cabling for Customer Premises (ISO/IEC 11801)
Commercial Building Telecommunications Cabling Standard (EIA/TIA 568)
Commercial Building Standard for Telecommunication Pathways and Spaces (EIA/TIA
569)
Administration Standard for Commercial Telecommunications Infrastructure (EIA/TIA
606)
Grounding and Bonding Requirements for Telecommunications in Commercial
Buildings (EIA/TIA 607)
Generic Cabling Systems for Information Technology (EN 50173)
Cabling Installation for Information Technology (EN 50174)
The bending radius of a power cable or a protection ground (PGND) cable is at least five
times the diameter of the cable.
The bending radius of an optical cable is at least 20 times the diameter of the optical
cable, and the minimum bending radius of the branch at each end of the optical cable is
30 mm.
The bending radius of the signal cable must be at least five times the diameter of the
cable.
Cables of the same type are bound together.
Different types of cables must be separately routed with a minimum spacing of 30 mm
and cannot be entangled or crossed.
The cables are bound tightly and neatly and the cable sheath is intact.
The cable ties face the same direction and all cable ties bound at similar positions must
be in a straight line.
The extra length of each indoor cable tie must be cut off. A slack of 5 mm is reserved for
each outdoor cable tie. All cut surfaces have no sharp edges.
Labels or nameplates are attached to both ends, joints, or turns of cables after they are
installed.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
6 Installing an RHUB
33