HUMIDIFIER
SUPPLY STATIC
INCLINE MANOMETER
AIRFLOW
Tools Needed:
1. Pitot Tube
2. Incline Manometer/Magnahelic
EXAMPLE 1
Return ESP after Filter
Supply ESP before Coil
Total ESP
Both Examples 1 and 2 are correct. Example 1 ESP readings were taken as laid out in static pressure reading location diagrams. (See Fig. 8-10).
Example 2 readings were taken as described. The coil and filter static pressure drops were taken from the manufacturer's product data sheets with
the assumption that 2000 CFM is being delivered.
Fig. 10—Downflow Total Static Pressure Reading Locations
0.20 in. wc
0.40 in. wc
0.60 in. wc
—39—
RETURN STATIC
ELECTRONIC
AIR CLEANER
INCLINE MANOMETER
A/C COIL
EXAMPLE 2
Return ESP before Filter
Filter Static Drop @ 2000 CFM
Supply ESP after Coil
Coil Static Pressure Drop Wet
Total ESP
CONDENSING
UNIT
A95365
0.10 in. wc
0.10 in. wc
0.20 in. wc
0.20 in. wc
0.60 in. wc