3: Installation
3.2.4

Storage

If you plan to store the UPS prior to its installation it should be kept (preferably in its shipping packaging) in a clean, dry
environment with a temperature between -25°C to +70°C and RH <90%. If the storage period is likely to exceed seven
days the packaging should be removed and the UPS inspected for shipping damage before it is placed into storage. If
there is no apparent damage you should refit the packaging or cover the UPS with a dust-cover to prevent the ingress of
dust and dirt.
Depending on the UPS model, the batteries can be housed within the UPS cabinet or an external battery cabinet/battery
rack. In the case of internally-mounted batteries, the batteries can be shipped already installed within a cabinet. Batteries
that are intended for external rack-mounting will be shipped in a separate package and should be stored under the
environmental conditions stipulated above.
3.2.5

Unpacking

WARNING: The UPS cabinet, battery cabinet (optional) and battery packages are heavy and may tip during
unpacking unless the unpacking instructions are not followed closely.
If the shipment is received in good order (i.e. the 'tip & tell' "FRAGILE" and "ARROW" indicators on the packing container
are intact) then unpack the UPS as follows:
1.
If the cabinet is shipped inside a wooden case, remove the screws at the base and sides of the case then carefully
remove the case from the from the package.
2.
Remove the plastic sheeting covering the UPS.
3.
Remove the external cabinet protection pieces (strengthened cardboard fillets, polystyrene foam etc.).
4.
Remove the anchor bolts securing the cabinet to the pallet then lift and remove the cabinet from the pallet.
5.
Retain the packaging materials for future shipment of the UPS.
6.
Examine the cabinet for any sign of damage and notify your supplier immediately if any damage is found.
7.
Open the cabinet door and verify that the UPS rating specifications on the nameplate located inside the door match
the order specification.
8.
Remove any accessories packages that are shipped inside the cabinet.
9.
Remove any internal protective packaging.
10. Ensure that all the UPS modules are correctly and securely fitted in their rack compartments.
11. Ensure that a protection cover is fitted to the front of any unpopulated UPS module rack compartment.
Batteries
CAUTION: The UPS batteries must ALWAYS be installed by the commissioning engineer.
If the batteries are shipped in a separate package they should remain in their packing until required by the Uninterruptible
Power Supplies Ltd. service engineer when the system is commissioned.
Battery life depends very much on the ambient temperature, and optimum battery life will be obtained if the batteries are
stored and operated at a temperature of 20°C.
WARNING: If the UPS is delivered without batteries, Uninterruptible Power Supplies Ltd. will not accept
responsibility for any damage or malfunctioning caused to the UPS by the incorrect storage, installation or
connection of batteries carried out by third parties.
24
TS_619_00 PW9000DPA S2 User Manual 13/3/17