Introduction; About This Document; Audience; Safety Warnings - Wave2wave Rome500 Hardware Installation Manual

Table of Contents

Advertisement

1

Introduction

1.1

About This Document

This guide provides step by step instructions for the installation of the Wave2Wave Robotic Optical
Management Engine (ROME) system, as well as important information on Standards, Agency193 Approvals,
and Safety warnings. Please read all the safety warnings before beginning installation.
1.2

Audience

This document is intended for technicians that install ROME.
1.3

Safety Warnings

Disposal: Separate Collection in European Countries
The following apply only to users in European countries:
This product is designated for separate collection at
an appropriate collection point. Do not dispose of as
household waste.
To avoid the potentially damaging effects on the
environment and human health as a result of the presence
of hazardous substances in electrical and electronic
equipment, end users of electrical and electronic equipment
should understand the meaning of the crossed-out wheeled
bin symbol. Do not dispose of WEEE as unsorted municipal
waste and have to collect such WEEE separately. This symbol
indicates that this product is to be collected separately.
For more information, contact the retailer or the local
authorities in charge of waste management.
Rack Certification
To ensure safety, all configurations of the rack cabinet
must be certified by a nationally recognized testing
laboratory in order to verify compliance with country-
specific safety regulations. This process ensures that
the end product remains safe for the operator and
service personnel under normal and foreseeable misuse
conditions.
Page 4
Heavy Equipment
Due to the heavy, 165 lbs (75 kg), weight of the ROME
Chassis and also to its slide out capability, it is important
that care is taken in lifting and mounting ROME to a rack.
To prevent bodily injury or damage to the chassis:
1. Never attempt to lift or tilt the chassis without the use
of a mechanical lifting device, such as the one pictured.
The lifter should support at least 100 kg.
2. Take special precautions to ensure that the system
remains stable.
a. The rack used to mount the ROME must be
properly anchored to the floor.
b. If the ROME unit is the only unit in the rack, it should
be mounted near the bottom of the rack (while still
allowing bottom clearance).
c. When mounting this unit in a partially filled rack,
when possible, load the rack from the bottom to the
top with the heaviest component at the bottom of
the rack.
d. To enable maintenance, the ROME Chassis should be
installed to allow 12 inches of clearance above and
below the chassis when fully extended on the slider.
e. If the rack is provided with stabilizing devices, install
the stabilizers before mounting or servicing the unit
in the rack.
www.wave-2-wave.com
Hardware
Installation Manual
DOC-0001

Hide quick links: