 For threaded attachment, avoid excessive tightening of the connections. Excessive force
may ruin the brazing where the connection is placed.
 For welded connections:
- Wrap a wet cloth at the base of the connection where the welding is done
- Use alloys containing an amount of silver over 40%.
5.2 FILTERS:
Install a filter higher than the exchanger to prevent particles and suspended solid materials from
entering the exchanger carried by the fluid. Clogging the canals may cause reduced performance,
an increase in load leaks and an increase in the risk of freezing. Select the filter keeping in mind
the minimum and maximum workload values of the exchanger.
Caution! Use a straining filter with passage holes not exceeding 90 mm.
5.3 ASSEMBLY FOR WATER-WATER APPLICATION
For applications of the type water-water, in order to obtain optimal performance conditions,
connect so that the flow of fluids is against the current, as shown in the illustration:
5.4 ASSEMBLY FOR APPLICATION WITH COOLANTS
For applications with coolants, install the exchanger in a vertical position.
IN
OUT
OUT
IN