Input Requirements
1. 90VAC to 132VAC
2. 47 to 63 Hz
Input AC tolerance +/- 20%. This means the charger will
operate satisfactorily in areas where the input voltage is low.
This charger is also suitable for every part of the world where
115VAC is used and for Japan where input is 100VAC.
Output
1. 1 Amp Constant Current @ 12 Volts DC. Equivalent to 2
Amps tapered charger in charging time.
2. Line regulation at Full Load = 1%
3. Load regulation @ 4%
4. Ripple Voltage – Very low 1%
The peak to peak ripple voltage into a resistive load is less
than 200mV for the output voltage above 12 VDC.
Charging Cycle
Stages
Condition
Stage 1
Charging Pulse
Mode
Stage 2
Constant
Current Mode
Stage 3
Constant
Voltage Mode
Stage 4
Standby Voltage
Mode
Recharging
Mode
Mode*
Pulse Mode
CC Mode
CV Mode
Standby
CV Mode
CC Mode
*CC Mode = Constant Current Charge
*CV Mode = Constant Voltage Charge
***See Stage 3 Description Below
Page 15
Current
Voltage
0.5 – 5.0V
1 A
Pulsing
5.0V – 14.7V
1A
Reduces
Holds @
from
14.7V
1A***
Reduces
Maintains
to Zero
13.6V
1A
12.5V
LED
Indication
Flash
Orange
Orange
Green
Orange