MINIMUM CLEARANCE TO COMBUSTIBLES AND NON-COMBUSTIBLES

MINIMUM CLEARANCE TO COMBUSTIBLE CONSTRUCTION FROM APPLIANCE AND VENT
SURFACES:
-
1/2" (13mm) to wall mounting plate
-
1" (2.5cm) to bottom and sides of vent pipe*
-
3" (7.6cm) to top of vent pipe*
MINIMUM CLEARANCES TO COMBUSTIBLES (FROM THE APPLIANCE):
-
15" (38.1cm) to top/ceiling
-
7" (17.8cm) to sides
-
6" (15.2cm) to bottom
-
1/2" (13mm) to rear
* A minimum of 1" (25mm) all around the vent pipe on all vertical runs to combustibles is required.
7"
(17.8 cm)
MIN.
36"
(91.4 cm)
MAX.
INSTALLATION
7"
(17.8 cm)
MIN.
4.5" (11.4 cm) MIN.
ALCOVE
TOP VIEW
15" (38.1 cm)
MIN.
6" (15.2 cm) MIN.
36"
(91.4cm)
MAX.
4.5" (11.4 cm) MIN.
ALCOVE
INSTALLATION
SIDE VIEW
25
15" (38.1 cm)
MIN.
6" (15.2 cm) MIN.
TYPICAL
INSTALLATION
W415-1606 / 09.09.16