Z8 will be controlling, how many stages the equipment has, how many zones are going to be conditioned, and what the square footage of each zone is for the size of the HVAC equipment. Because the Z8 uses wireless communication, plan installation locations appropriately for each Pelican device. Contact Pelican...
Page 5
Duct Pressure 10K ANALOG INPUTS Outside/Ambient Pressure Input Terminal Input Terminal Input Terminal Note: “T” Terminals can accept either Type 2 10K temperature probe or a Dry Contact Sensor input to send an alarm notification through your Pelican Site Manager.
LOCATION AND MOUNTING Location Choose a location for the Z8 that is not exposed to weather, and where controls and connections are accessible. The Wireless Module can be removed from the Z8 and is waterproof if installed onto a plastic electrical box with the provided gasket placed in-between (Reference Page 13).
Page 7
WARNING If installing the Wireless Module outside, make sure it is installed onto a PLASTIC electrical box. Make sure a proper seal is created between the Wireless Module, the provided gasket, and the contact edge of the plastic electrical box. Mounting examples are shown below are for reference.
Page 8
RETURN AIR PROBE VARIABLE SPEED BLOWER OUTSIDE AIR HANDLER WIRELESS ANTENNA Fig. 5 – Typical mounting dual duct system with VFD and economizer. DUCT STATIC PROBE Z8 (HOT DECK) SUPPLY AIR PROBE RETURN AIR PROBE HOT DECK SUPPLY RETURN AIR AIRFLOW...
Page 9
SUPPLY AIR PROBE Z8 (COLD DECK) CAUTION Always remove the Wireless Module if the Z8 is installed enclosed in metal (i.e.: inside the HVAC unit). The Wireless Module will not be able to communicate if metal is blocking its signal.
Static Pressure Tube Channel 3. If the Z8 is installed inside the HVAC unit or is enclosed in metal. The wireless module will need to be removed from the Z8 and installed either below the roof-line or outside the HVAC unit on a plastic weatherproof electrical box (Reference Pages 13 and 14 Figures 8 and 9).
Page 11
Fig. 17 shows the Z8 wired to a Heat Pump HVAC unit with a Bypass. (Page 22) k. Fig. 18 shows the Z8 wired to a Heat Pump HVAC unit with a Bypass and Economizer. (Page 23) l. Fig. 19 shows the Z8 wired to a Heat Pump HVAC unit with a VFD. (Page 24) m.
(reference Fig 4.3 and 4.4). In the case the system you are connecting the Z8 to is not defined in this installation guide. Contact Pelican Technical Support for assistance at 888-512-0490 or email support@pelicanwireless.com.
Page 14
ELECTRICAL BOX MUST BE PLASTIC AND PLACED OUTSIDE OF METAL ENCLOSURES. ELECTRICAL BOX MUST BE OUTDOOR RATED AND WEATHERPROOF. THREE WIRE BETWEEN WIRELESS MODULE AND Z8 CAN BE STANDARD UNSHIELDED COPPER THERMOSTAT WIRE UP TO 500 FEET (REF. PAGE 13 FIGURE 8).
Page 15
FOR DUAL DUCT APPLICATIONS, INSTALL ONE Z8 COMPRESSOR STAGE 1 RELAY TO MANAGE THE COLD SYSTEM AND A SECOND Z8 TO MANAGE THE HEAT SYSTEM (AS SHOWN HEAT STAGE 1 RELAY ON PAGE 8 FIGURE 5). IF THERE IS A SINGLE FAN,...
Page 16
FOR DUAL DUCT APPLICATIONS, INSTALL ONE Z8 COMPRESSOR STAGE 1 RELAY TO MANAGE THE COLD SYSTEM AND A SECOND Z8 TO MANAGE THE HEAT SYSTEM (AS SHOWN HEAT STAGE 1 RELAY ON PAGE 8 FIGURE 5). IF THERE IS A SINGLE FAN,...
Page 17
FOR DUAL DUCT APPLICATIONS, INSTALL ONE Z8 COMPRESSOR STAGE 1 RELAY TO MANAGE THE COLD SYSTEM AND A SECOND Z8 TO MANAGE THE HEAT SYSTEM (AS SHOWN HEAT STAGE 1 RELAY ON PAGE 8 FIGURE 5). IF THERE IS A SINGLE FAN,...
Page 18
FOR DUAL DUCT APPLICATIONS, INSTALL ONE Z8 COMPRESSOR STAGE 1 RELAY TO MANAGE THE COLD SYSTEM AND A SECOND Z8 TO MANAGE THE HEAT SYSTEM (AS SHOWN HEAT STAGE 1 RELAY ON PAGE 8 FIGURE 5). IF THERE IS A SINGLE FAN,...
Page 19
FOR DUAL DUCT APPLICATIONS, INSTALL ONE Z8 COMPRESSOR STAGE 1 RELAY TO MANAGE THE COLD SYSTEM AND A SECOND Z8 TO MANAGE THE HEAT SYSTEM (AS SHOWN HEAT STAGE 1 RELAY ON PAGE 8 FIGURE 5). IF THERE IS A SINGLE FAN,...
Page 20
FOR DUAL DUCT APPLICATIONS, INSTALL ONE Z8 COMPRESSOR STAGE 1 RELAY TO MANAGE THE COLD SYSTEM AND A SECOND Z8 TO MANAGE THE HEAT SYSTEM (AS SHOWN HEAT STAGE 1 RELAY ON PAGE 8 FIGURE 5). IF THERE IS A SINGLE FAN,...
Page 21
Heat Pump Wiring Guide The following wiring diagram is for heat pump control NOTE: TERMINAL DESIGNATIONS ARE DEFINED ON PAGE 5 COMPRESSOR STAGE 1 RELAY REVERSING VALVE (O/B) RELAY FAN ENERGIZE RELAY AUXILIARY HEAT RELAY COMPRESSOR STAGE 2 RELAY COMPRESSOR STAGE 3 RELAY TRANSFORMER 24VAC L1 (HOT)
Page 22
Bypass Wiring Guide (Heat Pump) The following wiring diagram is for a heat pump with a bypass. NOTE: TERMINAL DESIGNATIONS ARE DEFINED ON PAGE 5 COMPRESSOR STAGE 1 RELAY REVERSING VALVE (O/B) RELAY FAN ENERGIZE RELAY AUXILIARY HEAT RELAY COMPRESSOR STAGE 2 RELAY COMPRESSOR STAGE 3 RELAY TRANSFORMER 24VAC...
Page 23
Bypass and Economizer Wiring Guide (Heat Pump) The following wiring diagram is for a heat pump with a bypass and economizer. NOTE: TERMINAL DESIGNATIONS ARE DEFINED ON PAGE 5 COMPRESSOR STAGE 1 RELAY REVERSING VALVE (O/B) RELAY FAN ENERGIZE RELAY AUXILIARY HEAT RELAY COMPRESSOR STAGE 2 RELAY EXHAUST FAN RELAY...
Page 24
Variable Speed Fan Wiring Guide (Heat Pump) The following wiring diagram is for a heat pump with a variable speed fan (VFD). NOTE: TERMINAL DESIGNATIONS ARE DEFINED ON PAGE 5 COMPRESSOR STAGE 1 RELAY REVERSING VALVE (O/B) RELAY FAN ENERGIZE RELAY AUXILIARY HEAT RELAY COMPRESSOR STAGE 2 RELAY COMPRESSOR STAGE 3 RELAY...
Page 25
Variable Speed Fan and Economizer Wiring Guide (Heat Pump) The following wiring diagram is for a heat pump with a variable speed fan (VFD) and economizer. NOTE: TERMINAL DESIGNATIONS ARE DEFINED ON PAGE 5 COMPRESSOR STAGE 1 RELAY REVERSING VALVE (O/B) RELAY FAN ENERGIZE RELAY AUXILIARY HEAT RELAY COMPRESSOR STAGE 2 RELAY...
Page 26
Economizer Wiring Guide (Heat Pump) The following wiring diagram is for a heat pump with an economizer. NOTE: TERMINAL DESIGNATIONS ARE DEFINED ON PAGE 5 COMPRESSOR STAGE 1 RELAY REVERSING VALVE (O/B) RELAY FAN (SINGLE OR LOW SPEED) RELAY AUXILIARY HEAT RELAY COMPRESSOR STAGE 2 RELAY EXHAUST FAN RELAY COMPRESSOR STAGE 3 RELAY...
Page 27
DESIGNED AND RATED TO READ THE SUPPLY WATER TEMPERATURE OF THE CONTROL. DO NOT ENABLE BOILER CONTROL IF BOILER. TEMPERATURE DETECTION RANGE -20 DEG. F TO 180 DEG. F. USE THE T3 TEMPERATURE INPUT INSTEAD OF A TA1, UNLESS THIS Z8 IS CONTROLLING AN NO USING OPTION FROM ABOVE.
Number recorded, find the new notification on your Pelican Web App which matches the serial number on the Z8’s Wireless Antenna. Press configure. If no new notification is found, select Admin and identify if the new Z8 is on your Pelican Web App. If the Z8 is not found under Admin, then the Z8 is unable to communicate with the wireless gateway.
Page 29
MINIMUM STATIC Settable range 0.0 inch WC to 3.0 inch WC. This is a safety and will place the Z8 into an automatic reset if detected during a heating, cooling or reheat cycle. Reset will de-energize any calls for heating, cooling, or reheat, but the call for fan will remain energized.
Page 30
BOILER CONFIGURATION OPTIONS By enabling boiler control you are instructing the Z8 to use (W2) as a boiler enable output. With this feature active, the Z8 will NOT energize (W) until it detects the boiler’s supply water temperature to be within a specified range. This feature requires the Z8 to be able to read the boiler’s hot water supply temperature.
Blink Every 15 sec - Communicating Over Wireless Fig. 24 TROUBLESHOOT Z8 CONTROL OUTPUTS ON YOUR PELICAN SITE MANAGER YOU CAN TEST THE SIGNAL OUTPUTS OF THE Z8 TO PROVIDE IMMEDIATE FEEDBACK THAT EACH OF THE Z8’s OUTPUTS ARE CONTROLLING THE CORRECT INSTALLED EQUIPMENT.
Need help?
Do you have a question about the Z8 and is the answer not in the manual?
Questions and answers