Refrigerant Piping Insulation; Preparing Electrical Wiring; About Preparing Electrical Wiring; Installation - Daikin FDXM25F3V1B Installer's Reference Manual

Split system air conditioners
Hide thumbs Also See for FDXM25F3V1B:
Table of Contents

Advertisement

Model
L1 Liquid piping
FDXM25+35
Ø6.4
FDXM50+60
Ø6.4
5.3.2

Refrigerant piping insulation

▪ Use polyethylene foam as insulation material:
▪ with a heat transfer rate between 0.041 and 0.052 W/mK (0.035
and 0.045 kcal/mh°C)
▪ with a heat resistance of at least 120°C
▪ Insulation thickness
Pipe outer diameter
Insulation inner
)
diameter (Ø
p
6.4 mm (1/4")
8~10 mm
9.5 mm (3/8")
12~15 mm
12.7 mm (1/2")
14~16 mm
Ø
Ø
i
i
Ø
Ø
p
p
t
If the temperature is higher than 30°C and the humidity is higher
than RH 80%, the thickness of the insulation materials should be at
least 20  mm to prevent condensation on the surface of the
insulation.
5.4

Preparing electrical wiring

5.4.1

About preparing electrical wiring

INFORMATION
Also read the precautions and requirements in the
"General safety precautions" chapter.
WARNING
▪ If the power supply has a missing or wrong N-phase,
equipment might break down.
▪ Establish proper earthing. Do NOT earth the unit to a
utility pipe, surge absorber, or telephone earth.
Incomplete earthing may cause electrical shock.
▪ Install the required fuses or circuit breakers.
▪ Secure the electrical wiring with cable ties so that the
cables do NOT come in contact with sharp edges or
piping, particularly on the high-pressure side.
▪ Do NOT use taped wires, stranded conductor wires,
extension cords, or connections from a star system.
They can cause overheating, electrical shock or fire.
▪ Do NOT install a phase advancing capacitor, because
this unit is equipped with an inverter. A phase
advancing capacitor will reduce performance and may
cause accidents.
WARNING
▪ All wiring must be performed by an authorized
electrician and must comply with the applicable
legislation.
▪ Make electrical connections to the fixed wiring.
▪ All components procured on the site and all electrical
construction
must
legislation.
WARNING
ALWAYS use multicore cable for power supply cables.
FDXM25~60F3V1B
Split system air conditioners
4P482333-1 – 2017.03
L1 gas piping
Ø9.5
Ø12.7
Insulation thickness
)
(t)
i
≥10 mm
comply
with
the
applicable
6

Installation

6.1

Overview: Installation

This chapter describes what you have to do and know on-site to
install the system.
Typical workflow
Installation typically consists of the following stages:
▪ Mounting the outdoor unit.

▪ Mounting the indoor unit.

▪ Connecting the refrigerant piping.
▪ Checking the refrigerant piping.
▪ Charging refrigerant.
▪ Connecting the electrical wiring.
▪ Finishing the outdoor installation.
▪ Finishing the indoor installation.
INFORMATION
This chapter only describes installation instructions specific
to the indoor unit. For the other instructions, see:
▪ The installation manual of the outdoor unit
▪ The installation manual of the user interface
▪ The installation manual of the optional accessories
6.2
Mounting the indoor unit
6.2.1
Precautions when mounting the indoor
unit
INFORMATION
Also read the precautions and requirements in the
following chapters:
▪ General safety precautions
▪ Preparation
6.2.2

Guidelines when installing the indoor unit

INFORMATION
Optional equipment. When installing optional equipment,
also read the installation manual of the optional equipment.
Depending on the field conditions, it might be easier to
install the optional equipment first.
▪ Ceiling strength. Check whether the ceiling is strong enough to
support the weight of the unit. If there is a risk, reinforce the ceiling
before installing the unit.
▪ For existing ceilings, use anchors.
▪ For new ceilings, use sunken inserts, sunken anchors or other
field supplied parts.
▪ Suspension bolts. Use W3/8 M10 suspension bolts for
installation. Attach the hanger bracket to the suspension bolt. Fix it
securely using a nut and washer from the upper and lower sides
of the hanger bracket.
▪ Ceiling opening size. Make sure the ceiling opening is within the
following limits:
6 Installation
Installer reference guide
9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fdxm35f3v1bFdxm50f3v1bFdxm60f3v1b

Table of Contents