Santerno sinus M User Manual page 163

Variable frequency drive
Hide thumbs Also See for sinus M:
Table of Contents

Advertisement

11.5.1
A, B Contact selection
LED
Parameter name
display
A, B Contact
I91
selection
This function code is for selecting the Contact type of multifunction transistor Digital output MO.
-
MO contact type is A contact (normally open) when setting value is "0", and B contact (normally
closed) when setting value is "1".
Multifunction relay digital output 3 A,B,C does not need this function, because this relay has
-
already both A, B Contacts.
11.5.2
A, B Contact On/Off delay
LED
Parameter
display
name
I92
MO On delay
I93
MO Off delay
30A,B,C On
I94
delay
30A,B,C Off
I95
delay
These codes are for On, off delay time of multi functional transistor Digital output MO and Relay
-
Digital output 3 A,B,C.
If the operation time of the contact is shorter than the delay time, operation is as shown below.
-
Internal
operation
Real
Operation
On Delay time
Setting
range
0
A Contact (Normal open)
1
B Contact (Normal Close)
Setting
range
0.0~10.0 sec MO contact On delay time
0.0~10.0 sec MO contact Off delay time
0.0~10.0 sec 30 A,B,C contact On delay time
0.0~10.0 sec 30 A,B,C contact Off delay time
Off Delay time
11-13
Description
Description
Internal
Operation
Real
Operation
On Delay time
Adj.
Factory
During
defaults
run
0
O
Adj.
Factory
During
defaults
Run
0.0 sec
X
0.0 sec
X
0.0 sec
X
0.0 sec
X
Off Delay time

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents