Refrigerant Piping System; Pipe Connection Method Between Outdoor Unit/Indoor Unit - LG ARUN080LTE4 Installation Manual

Hide thumbs Also See for ARUN080LTE4:
Table of Contents

Advertisement

12

Refrigerant piping system

1 Outdoor Units
Y branch method
Ⓐ : Outdoor Unit
Ⓑ : 1st branch (Y branch)
Ⓒ : Indoor Units
Combination of Y
branch/header Method
Ⓐ : Outdoor Unit
Ⓑ : 1st branch (Y branch)
Ⓒ : Y branch
Ⓓ : Indoor Unit
Ⓔ : Header
Ⓕ : Sealed piping
Header Method
Ⓐ : Outdoor Unit
Ⓑ : 1st branch
Ⓒ : Indoor Units
Ⓓ : Sealed piping
Ⓔ : Header
Series Outdoor Units (2 Units ~ 4 Units)
Y branch method
Ⓐ : Outdoor Unit
10m or
Ⓑ : 1st branch (Y branch)
less
Ⓒ : Indoor Units
Ⓓ : Downward Indoor Unit
Ⓔ : Connection branch
pipe between Outdoor
units: ARCNN41
Ⓕ : Connection branch
pipe between Outdoor
units : ARCNN31
Ⓖ : Connection branch
pipe between Outdoor
units : ARCNN21
Combination of Y branch/
header Method
Ⓐ : Outdoor Unit
10m or
less
Ⓑ : 1st branch(Y branch)
Ⓒ : Y branch
Ⓓ : Indoor Unit
Ⓔ : Connection branch pipe
between Outdoor
units : ARCNN41
Ⓕ : Connection branch pipe
between Outdoor
units : ARCNN31
Ⓖ : Connection branch pipe
between Outdoor
units : ARCNN21
Ⓗ : Header
Ⓘ : Sealing
Indoor
Unit
L150m (200 m : Conditional application)*
l 40m (90 m : Conditional application)*
h 40m
h * : See Table 4
L150m (200 m : Conditional application)*
l 40m (90 m : Conditional application)*
h * : See Table 4
L200m
l 40m
h 40m
ODU Capacity
Master ≥ Slave 1 ≥Slave 2 ≥Slave 3
Slave3
Slave2
Slave3
Slave1
Slave2
Master
Slave1
Master
L150m (200 m : Conditional application)*
l 40m (90 m : Conditional application)*
h 40m
h * : See Table 4
ODU Capacity
Master ≥ Slave 1 ≥Slave 2 ≥Slave 3
Slave3
Slave3
Slave2
Slave2
Slave1
Slave1
Master
Master
L150m (200 m : Conditional application)*
l 40m (90 m : Conditional application)*
h * : See Table 4
Header Method
Ⓐ : Outdoor Unit
Ⓑ : Header branch
Ⓒ : Indoor Units
Ⓓ : Sealing
Ⓔ : Connection branch pipe
between Outdoor
units : ARCNN41
Ⓕ : Connection branch pipe
between Outdoor
units : ARCNN31
Ⓖ : Connection branch pipe
between Outdoor
units : ARCNN21
Pipe Connection Method between outdoor
unit/indoor unit
Master
L2
L3
Indoor
Unit
1st branch
l 40m
h 40m
h See Table 2
A : Refrigerant pipe diameter from outdoor unit to first branch
E : Refrigerant pipe diameter for outdoor unit capacity
(Slave 1+ Slave 2+ Slave 3)
F : Refrigerant pipe diameter for outdoor unit capacity
(Slave 2+ Slave 3)
G : Refrigerant pipe diameter for outdoor unit capacity(Slave 3)
Level Difference
(Outdoor unit ↔ Outdoor unit)
Max length from first branch to
each outdoor unit (L1, L2, L3)
Indoor
Unit
(Table 1) Limit Pipe length
Longest
length(L)
Outdoor Unit
Max pipe
length
Equivalent
Indoor Unit
pipe length
Total pipe
Outdoor Unit
Difference in
Max
↔ Indoor Unit
height(H)
difference
in height
Indoor Unit
Difference in
↔ Indoor Unit
Longest pipe
length after
length(l)
1st branch
h * : See Table 4
!
WARNING
Increased Pipe Diameter(table 2)
- When pipe length is 90m or more from ODU to 1st branch
- When level difference is 50m or more
Slave3
Slave2
Slave1
Slave3
10m or
Slave2
Master
less
h 40m
Slave1
Slave2
H1
L1
Refrigerant pipe diameter from outdoor unit to first branch
5m
Less than 10m
(equivalent length of piping 13m)
Combination of Y
Y branch
branch/header
Method
Method
A+B+b≤150 m
A+B+C+D+e≤150 m
A+C+e≤150 m
pipe
(200 m: Conditional
(200 m: Conditional
application)*
application)*
175 m
175 m
(225 m: Conditional
(225 m: Conditional
application)*
application)*
1,000 m
1,000 m
length
110 m
110 m
40 m
40 m
height(h)
40 m
40 m
Pipe
(90 m: Conditional
(90 m: Conditional ap-
application)*
plication)*
ODU Capacity
Master ≥ Slave 1 ≥Slave 2 ≥Slave 3
Slave1
Master
L200m
l 40m
Slave3
Header
Method
A+f≤200 m
225 m
1,000 m
110 m
40 m
40 m