IDU capacity adjusting
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button :
"Func" Push the '●' button
Select the Function using '▶', '◀' Button :
"Fn7" Push the '●' button
Select the Option using '▶', '◀' Button :
"on" ~ "oFF" Push the '●' button
IDU capacity adjusting is set
!
CAUTION
• Ask an authorized technician to setting a function.
* ARUN***LTS4 models operate only overall defrost function.
Target pressure adjusting
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button :
"Func" Push the '●' button
Select the Function using '▶', '◀' Button :
Select the Function using '▶', '◀' Button :
"Fn8" Push the '●' button
"Fn8" Push the '●' button
Select the Option using '▶', '◀' Button :
"HEAT" , "COOL" Push the '●' button
Select the Option using '▶', '◀' Button :
"op1" ~ "op4" Push the '●' button
Target pressure is set
Setting
Purpose
Mode
Heat
op1 Increase capacity
Increase capacity
Decrease power
op2
Increase capacity
consumption
Decrease power
Decrease power
op3
consumption
consumption
Decrease power
Decrease power
op4
consumption
consumption
!
CAUTION
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• Change a power consumption or capacity.
Condensing
Evaporating
temperature
temperature
Cool
variation
variation
+2 °C
-3 °C
-2 °C
-1.5 °C
-4 °C
+2.5 °C
-6 °C
-4.5 °C
Comfort Operation
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button :
"Func" Push the '●' button
Select the Function using '▶', '◀' Button :
"Fn9" Push the '●' button
Select the Option using '▶', '◀' Button :
"on" ~ "oFF" Push the '●' button
Comfort Operation mode is set
!
CAUTION
• Ask an authorized technician to setting a function.
* If do not use a function, set an off-mode.
27