BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (economizer, wet coil, etc.).
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.).
See page 13 for blower motors and drives and page 14 for wet coil and options/accessory air resistance data.
Air
0.10
Volume
RPM
BHP
RPM
cfm
1900
853
0.41
886
2000
883
0.48
913
2100
906
0.56
936
2200
930
0.64
960
2300
954
0.72
985
2400
981
0.81
1013
2500
1010
0.91
1042
2600
1040
1.01
1073
2700
1072
1.10
1104
2800
1105
1.21
1137
2900
1138
1.32
1169
Air
0.90
Volume
RPM
BHP
RPM
cfm
1900
1126
0.77
1163
2000
1148
0.84
1183
2100
1170
0.92
1206
2200
1195
1.00
1230
2300
1220
1.08
1254
2400
1245
1.18
1278
2500
1271
1.28
1303
2600
1297
1.39
1328
2700
1323
1.52
1353
2800
1351
1.65
1380
2900
1379
1.79
1407
BELT DRIVE KIT SPECIFICATIONS
Model No.
Nominal
036
1.5
048
1.5
060
1.5
072
1.5
NOTE - Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor hp required. Maximum usable hp of
motors furnished are shown. In Canada, nominal motor hp is also maximum usable motor hp. If motors of comparable hp are used, be sure to keep within the service
factor limitations outlined on the motor nameplate.