Blower Operation And Adjustments - Lennox LHT180 Installation Instructions Manual

Hide thumbs Also See for LHT180:
Table of Contents

Advertisement

Blower Operation and Adjustments

Supply Air Staged Units - The blower rotation will
always be correct on units equipped with an inverter.
Checking blower rotation is not a valid method of
determining voltage phasing for incoming power.
Supply Air Staged Units and Units Equipped With
Optional Voltage or Phase Detection - The Unit
Controller checks the incoming power during start-up. If
the voltage or phase is incorrect, the Unit Controller will
display an alarm and the unit will not start.
A-Blower Operation
Refer to the Unit Controller Setup Guide to energize
blower. Use this mobile service app menu:
SERVICE > TEST > BLOWER
Instructions provided with the thermostat may also be
used to initiate blower only (G) demand. Unit will cycle on
thermostat demand. The following steps apply to
applications
using
a
thermostat.
1- Blower operation is manually set at the thermostat
subbase fan switch. With fan switch in ON position,
blowers will operate continuously.
2- With fan switch in AUTO position, the blowers will
cycle with demand. Blowers and entire unit will be off
when system switch is in OFF position.
IMPORTANT
Three Phase Scroll Compressor Voltage Phasing
Three phase scroll compressors must be phased se­
quentially to ensure correct compressor and blower*
rotation and operation. Compressor and blower are
wired in phase at the factory. Power wires are color-
coded as follows: line 1-red, line 2-yellow, line 3-blue.
1-Observe suction and discharge pressures and blow­
er* rotation on unit start-up.
2-Suction pressure must drop, discharge pressure must
rise and blower* rotation must match rotation marking.
If pressure differential is not observed or blower* rota­
tion is not correct:
3-Disconnect all remote electrical power supplies.
4-Reverse any two field-installed wires connected to
the line side of S48 disconnect or TB13 terminal strip.
Do not reverse wires at blower contactor.
5-Make sure the connections are tight.
Discharge and suction pressures should operate at
their normal start‐up ranges.
*Supply air inverter blower motors should rotate in the
correct direction; verify scroll compressor rotation
separately. Contact technical support if the blower is
rotating incorrectly.
LHT/LDT180, 240
typical
electro-mechanical
1-Make sure that unit is installed in accordance with the
installation instructions and applicable codes.
2-Inspect all electrical wiring, both field‐ and factory‐
installed, for loose connections. Tighten as required.
3-Check to ensure that refrigerant lines do not rub against
the cabinet or against other refrigerant lines.
4-Check voltage at disconnect switch. Voltage must be
within range listed on nameplate. If not, consult power
company and have voltage condition corrected before
starting unit.
5-Make sure filters are new and in place before start‐up.
B-Blower Access
1- Disconnect jack/plug connector to blower motor. Also
disconnect jack/plug connector heating limit switches
on gas units.
2- Remove screws on either side of blower assembly
sliding base. See figure 12.
3- Pull base toward outside of unit.
C-Determining Unit CFM
IMPORTANT - Multi-staged supply air units are
factory-set to run the blower at full speed when there is a
blower (G) demand without a heating or cooling
demand. Refer to the field-provided, design specified
CFM for all modes of operation. Use the following
procedure to adjust motor pulley to deliver the highest
CFM called for in the design spec. See Inverter Start-Up
section to set blower CFM for all modes once the motor
pulley is set.
1- The following measurements must be made with a
dry indoor coil. Run blower (G demand) without a
cooling demand. Measure the indoor blower shaft
RPM. Air filters must be in place when measurements
are taken.
2- With all access panels in place, measure static
pressure external to unit (from supply to return).
Blower performance data is based on static pressure
readings taken in locations shown in figure 11.
Note - Static pressure readings can vary if not taken
where shown.
3- Referring to the blower tables, use static pressure
and RPM readings to determine unit CFM. Use the
accessory air resistance table when installing units
with any of the optional accessories listed.
Page 12
WARNING

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ldt180Lht240Ldt240

Table of Contents