Speci cation
CMi210
Insulation Clamp Meter
Insulation Resistance Operating Range to BS EN 61557-2
Operating range to
Test voltage
BS EN 61557-2 (See note 1)
55k to 300k
0.55M to 3M
50V
5.5M to 30M
55M to 300M
100k to 600k
0.6M to 6M
100V
6 M to 60M
60M to 600M
0.5M to 1.5M
5M to 15M
250V
50M to 150M
0.5G to 1.5G
0.5M to 3 M
5M to 30M
500V
50M to 300M
0.5G to 3G
1M to 6M
6M to 60M
1000 V
60M to 600M
2.5G to 6G
Speci cation
CMi210
Insulation Clamp Meter
ENVIRONMENTAL
Temperature & Humidity (Operating): 0°C to 50°C <70% R.H.
(Storage): -20°C to 60°C < 80% R.H.
Altitude: up to 2000m
Pollution degree 2, indoor use
SAFETY
Conforms to:
BS EN 61010-1, BS EN 61010-2-032, CAT IV 600V, CAT III 1000V
BS EN 61557-1, BS EN 61557-2, CAT II 600V
Class II, Double insulation
EMC
Conforms to BS EN 61326-1, BS EN 61326-2-2
SPECIFICATION FOR TL45 TEST LEADS
Maximum voltage: 1000V AC/DC
Maximum current: 10A continuous
Connector: 4mm banana plug with fi xed shroud
Environmental
Temperature (Operating & Storage): 0°C to 40°C
Altitude: up to 2000m
Pollution degree 2
Safety
Conforms to BS EN 61010-031,
CAT IV 600V, CAT III 1000V, 10A (Probe tip caps fi tted)
CAT II 1000V, 10A (Probe tip caps removed)
Class II, Double insulation
Note 1: The operating range where the operating uncertainty does not exceed
± 30 % in accordance with BS EN 61557-2.
Operating uncertainty (B) = ± (|A| + 1,15 [ E
where, A is the intrinsic uncertainty at reference conditions
Test voltage accuracy: 0% to +20%
Short circuit test current: 1mA
Auto discharge: discharge time <1s for C=1μF or less
Maximum capacitive load: operable with up to 1μF load
Live circuit detection: >30V DC or AC rms, test is inhibited
Overload protection: 600V DC or AC rms

GENERAL

Display: liquid crystal display
digital, 6000 counts, updates 2/sec
polarity: Automatic, positive implied, '-' for negative polarity indication
overrange: (OL) or (-OL) is displayed
bar-graph, 60 segments, updates 20/sec
Power: 5 x 1.5V, AA alkaline batteries (IEC LR6, NEDA 15A)
Battery life: 100 hours typical with alkaline

Low battery indication:

Auto power off: after 30 minutes
Fuse: 0.5 A/1000V 6.3x32mm fast blow ceramic fuse
Jaw opening capability: conductor diameter 57mm
Dimensions: 326 x 108 x 53mm
Weight: 720g approx., including batteries
Includes: carrying case, set of TL45 test leads, probe set, Type K
thermocouple, 5 x 1.5V AA batteries (installed), instructions
16/06/2014 11:40:20
CMi210 instructions rev1.indd 5
Check out what else you can get from Martindale:
17th Edition Testers
Accessories
Calibration Equipment
Continuity Testers
Electricians' Kits
Environmental Products
Full Calibration & Repair Service
Fuse Finders
Digital Clamp Meters
Digital Multimeters
Labels
Microwave Leakage Detectors
Tel: +44 (0)1923 441717 Fax: +44 (0)1923 446900
Speci cation
CMi210
Insulation Clamp Meter
2
E
is the variation due to supply voltage change
2
E
is the variation due to temperature change
3
symbol and bAtt displayed
bus bar 70 x 18mm
Motor Maintenance Equipment
Multifunction Testers
Non-trip Loop Testers
Pat Testers & Accessories
Phase Rotation Testers
Proving Units
Socket Testers
Thermometers & Probes
Test Leads
Voltage Indicators
Specialist Metrohm Testers (4 & 5kV)
Specialist Drummond Testers
Martindale Electric Company Limited
Metrohm House, Imperial Park, Imperial Way,
Watford, Hertfordshire, WD24 4PP, UK
E-mail: sales@martindale-electric.co.uk
Website: www.martindale-electric.co.uk
© 2016 Martindale Electric Company Ltd.
Registered in England No. 3387451.
LITCMi210 REV1
2
2
+ E
] )
3
16/06/2014 11:40

Advertisement

Table of Contents
loading

Table of Contents