Outdoor Unit (80 / 90 Class)
Step
Make sure there is no
refrigerant gas left inside
the refrigerant pipes
before starting the job.
When heating up the
brazed parts, make sure
to carry out the N2
replacement.
5
Remove the 2 sheets of
putty.
6
Disconnect the brazed
part (a) at discharge
side of the compressor.
Disconnect the brazed
7
part (b) at suction side
of the compressor.
294
Procedure
Si12-714
Points
Warning
The compressor's refrigerating
machine oil may catch fire. Have
wet cloth at hand for quickly
putting out the fire.
Warning
If refrigerant gas leaks during the
job, ventilate the room. (Bear in
mind that if the refrigerant gas is
exposed to open flames, noxious
gas may be generated.)
Caution
Be careful not to get yourself
burnt with the pipes and other
parts that are heated by the gas
welding rod.