8/12 to 12/12 roof terminal kit GD-111, fl at roof terminal kit GD-112 or periscope kit GD-201 (for wall penetration
below grade). With fl exible venting, in conjunction with the various terminations, use either the 5 foot (1.5m) vent
kit GD-220 or the 10 foot (3.1m) vent kit GD-330. For stoves only: wall terminal kit GD-175 (venting included).
venting requirements
EN
For optimum fl ame appearance and appliance performance, keep the vent length and number of elbows to a
minimum.
The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to
verify that it is unobstructed and undamaged.
Rigid and fl exible venting systems must not be combined. Different venting manufacturer components
must not be combined.
These vent kits allow for either horizontal or vertical venting of the appliance. The maximum allowable horizontal
run is 20 feet (6.1m). The maximum allowable vertical vent length is 40 feet (12.2m). The maximum number of vent
connections is two horizontally or three vertically (excluding the appliance and the air terminal connections) when
using fl exible venting.
Horizontal runs may have a 0" rise per foot or 0mm rise per meter however for optimum performance it is
recommended that all horizontal runs have a minimum 1/4" rise per foot or 21mm rise per meter using fl exible
venting. For safe and proper operation of the appliance, follow the venting instructions exactly.
A terminal shall not terminate directly above a sidewalk or paved driveway which is located between two single
family dwellings and serves both dwellings. Local codes or regulations may require different clearances.
Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 1¼"
(31.8mm) air gap all around between the inner liner and outer liner is required for safe operation.
7.1A
3.1

typical venting installation

16" (40.6cm)
MINIMUM
40 FT (12M)
MAXIMUM
18" (45.7cm)
3 FT (1M)
MAXIMUM
MINIMUM
12 7/8"
(32.7cm)
MINIMUM
46" (116.8cm)
MINIMUM
PLUS RISE *
*See "venting requirements" and "venting installation" sections
13
W415-1705 / A / 07.13.17