ELECTRICAL WIRING (MILLIVOLT)
CONNECTING REMOTE RECEIVER
1. Set remote receiver. See instructions included in receiver kit.
2. Connect the two (2) 1/4"
female connectors to the
TP/TH and TH terminals
on the control valve.
3. Connect the four-pin
connector from the valve
motor to the four-pin con-
nector on the receiver.
4. For further instruction
refer to instruction sheet
included with RCSIT
Remote.
Do not allow wires
to touch grate or
Note: Heat reduces battery life. You can protect the receiver and extend battery life by mounting receiver
The Millivolt system and individual
components may be checked with a
Millivolt meter having a 0-1000 mV
range. Conduct each check shown in
chart below by connection meter test
leads to terminals as indicated.
("A" Reading - Thermostat contacts CLOSED - Control Knob "ON" - Main burner should turn ON)
a. If the reading is more than 175 Millivolts and the automatic valve still does not come on, replace the con-
trol.
b. If the closed circuit reading ("A" reading) is less than 175 Millivolts, determine cause for low reading, pro-
ceed to Section B below.
pilot voltage, 500 Millivolts minimum. If the minimum Millivolt reading is not obtainable, replace pilot.
22
Figure 17 -
Installing Remote Receiver
CHECK
TEST
TO TEST
COMPLETE
A
SYSTEM
THERMOPILE
B
OUTPUT
Valve
Remote Receiver
CONNECT
SWITCH OR
METER LEADS
THERMOSTAT
TO TERMINALS
CONTACTS
2 & 3
CLOSED
1 & 2
OPEN
Connectors
Motor
FP2010
METER
READING
SHOULD BE
MINIMUM 175
MINIMUM 500