Equipment Profiles
EEP: A5-07-01

Technical Specifications

Power Supply
Operational Light Level
Charging Period
Initial Operation
Full Charge Operation
Telegram Transmission
Telegram Heartbeat Period
Communications
Antenna
Transmission Range
Inputs
Outputs

Mechanical Specifications

Optimal Operating Temperature
Relative Humidity
Weight
Dimensions
Occupancy Sensor - PIR ON, PIR OFF
Solar cell, optional battery (CR2032)
backup,Operational Light Level
30 lux (3 foot candles) minimum
Initial Operation
6 hours full charge at 200 lux (19
foot candles)Telegram Transmission
Telegram Heartbeat Period
60 seconds in 30 lux ( 3 foot candles)
minimum 60 hours in 0 lux after 6
hours @ 200 lux charging period
on motion or on heartbeat period
110 seconds ± 20 seconds
315 MHz EnOcean radio
Integrated whip
30m (100 ft.) - commercial office space
LINK button for assignment to receiver
Walk-Test LED
32°F to 86°F (0°C to 30°C)
5% to 93% RH (non-condensing)
3.7 oz. (104 gms.)
4.8" diameter, 1.5" height
(122 mm x 38)