4-1-4 Setting an indoor unit installation option
(Suitable for the condition of each installation location)
1. Check whether power is supplied or not.
- When the indoor unit is not plugged in, there should be additional power supply in the indoor unit.
2. The panel(display ) should be connected to an indoor unit to receive option.
3. Set the installation option according to the installation condition of an air conditioner.
- The default setting of an indoor unit installation option is 02000-100000-200000-300000.
- Individual control of a remote controller(SEG20) is the function that controls an indoor unit individually when there is more
than one indoor unit.
4. Set the indoor unit option by wireless remote controller.
SEG1
0
SEG7
1
SEG13
2
External control
SEG19
Individual control of
3
a remote controller
▶
Drain pump(SEG8) will be set to 'USE + 3 minute delay' even if the drain pump is set to 0.
▶
Number of hours using filter(SEG18) will be set to '1000 hour' even if the SEG18 is set to except for 2 or 6.
▶
4-6
SEG2
SEG3
2
RESERVED
SEG8
SEG9
Drain pump
RESERVED
SEG14
SEG15
External control
output
SEG20
SEG21
RESERVED
SEG4
Exterior temperature
Central control
sensor
SEG10
RESERVED
RESERVED
SEG16
S-Plasma ion
SEG22
RESERVED
RESERVED
Indoor Unit
1(L)
F2
2(N)
F1
SEG5
SEG6
RESERVED
SEG11
SEG12
RESERVED
SEG17
SEG18
Number of hours
Buzzer
using filter
SEG23
SEG24
RESERVED
Samsung Electronics