MCAC-UTSM-2009-03
10. Troubleshooting
10.1 Indoor Unit Malfunction
Indoor unit display panel
No.
Running lamp
1
☆
2
×
3
☆
4
×
5
☆
6
☆
(× Extinguish,
Flash at 5Hz,
☆
1. Running lamp flash at 5Hz
Running lamp flash at 5Hz
Judge: Room temp. sensor checking channel is abnormal
Validate: Check whether the resistance of the room
temp. sensor is correct according to Annex 1
Replace the indoor main board
Outdoor Units
Timer lamp
Defrosting lamp
×
×
×
☆
☆
☆
×
☆
●
☆
☆
●
● Light)
Yes
Malfunction
Room temp. sensor checking channel is abnormal
Evaporator temp. sensor checking channel is abnormal
Condenser temp. sensor checking channel is abnormal
In-outdoor unit communication malfunction
DC Fan malfunction
EEPROM malfunction
No
Replace the room temp. sensor
Troubleshooting
29