Sample of outdoor installation with shelter
H=ALTEZZA G.E.
H=HEIGTH G.S.
H=HAUTEUR G.E.
H=ALTEZA G.E.
INDOOR INSTALLATION
In order to avoid endangering or damaging genset following
indications must be followed.
Genset installation location has to be in accordance to the
norms in force.
ref.
Description
1
Generating set
2
Auxiliary aspirator
5
Exhaust pipe
7
Exhaust pipe protection and insulation
8
Raincover and anti-intrusion grid
9
Exhaust conduit
11
Location area with isolated foundation
12
Air inlet with anti-intrusion grid
13
Entrance door
14
Containment step
Minimum suggested dimension table
A
Length G.E. + 1000 mm
B
Width G.E. + 2000 mm
C
Width G.E. + 200 mm
D
Length G.E. + 400 mm
E
Width G.E. + 400 mm
H
Height G.E. + 1500 mm (>2500 mm)
Note: dimensions required by norms in force have to be re-
spected in any case.
SURFACE AREA
The best solution is to create a base isolated from the rest of
the structure, on which the genset will be located, in order to
avoid vibrations being transmitted.
The base must be built with reinforced concrete and there
must be the possibility to fix the genset to it by using screw
anchors or rag bolts.
Base dimensions should exceed genset dimensions of at least
200 mm on each side. Base should weigh three times static
genset weight (indicated on the technical date).
INSTALLATION INSTRUCTIONS
Floor should be levelled and suitable to sustain genset weight.
Thresholds on doors and openings should have a barrier in or-
der to avoid liquids leaking. In case it is not possible to provide
a door with a barrier, the genset should have a collection base
appropriate for the quantity of liquid it contains, in any case
dimensions of collection base must be in accordance to the
laws in force in country of installation.
ROOM OPENINGS AND VENTILATION
The room should have a ventilation system sufficient enough
to avoid stagnation and circulation of overheated air.
Openings for incoming and outgoing air should be of appro-
priate size, considering minimum required air flow and maxi-
mum back pressure, values that can be checked on the engine
manual.
Opening for the air entrance should be near the back part of
the genset as close as possible to the ground.
If openings for air flow are not aligned with genset it may be
necessary to add air conduits to avoid any air dispersion (see
figure).
17
M
2.6.2