Operating guide
Termix One Solar

6.0 Controls

6.1 DHW temperature control

DHW temperature control
There are various types of DHW temperature control used in
Danfoss substations.
DHW temperature should be adjusted to 45-50 °C, as this provides
optimal utilisation of DH water. At DHW temperatures above 55 °C,
the possibility of lime scale deposits increases significantly.
6.1.1 AVTB controller (20–60 °)
The temperature setting is as follows:
1 = 20 °C
2 = 35 °C
3 = 50 °C
4 = 60 °C
5 = 70 °C
The values are intended as a guide.
The AVTB operates at its best at DH supply temperatures of up to
90 °C.
Thermostatic control
DHW temperature is adjusted as follows:
To increase temperature, turn the handle on the thermostatic
controller to select a higher number.
To decrease temperature, turn the handle on the thermostatic
controller to select a lower number.
6.1.2 Circulator pump UPM3
UPM3 Pumps can be controlled in constant pressure, proportional
pressure or constant speed mode defined by the means of a smart
user interface.
The variable speed modulating modes allow the pump to match its
performance to the system requirements, helping to reduce noise
when thermostatic valves are closing down.
Energy labelling class A
Danfoss District Energy
10