Contrec 202D User Manual page 9

Field mounted rate totaliser
Table of Contents

Advertisement

Relay Outputs
The outputs can be connected to IS circuits with the following
maximum values:
Ui = 28V
Ii = 93mA
Pi = 653mW
The internal capacitance and inductance seen on these terminals is 0.1uF
and 0mH.
Flowmeter Input
Entity parameters on the flowmeter enable connection to a wide
range of approved sensors.
Input parameters are:
Ui = 24V
Ii = 20mA
Pi = 320mW
The internal capacitance and inductance seen on these terminals is 0.02uF
and 0mH.
Output parameters are:
Uo = 10.0V (open circuit)
Io = 9.0mA (short circuit)
Po = 23mW
Maximum allowed external capacitance is 20µF.
Maximum allowed external inductance is 1.5H.