Repairs, Spare Parts; Troubleshooting - Airflow Duplexvent Flexi DV1600 Installation, Use And Maintenance Manual

Ventilation units with heat recovery
Table of Contents

Advertisement

Failure
- Cool air is supplied
Appliance does not
continuously
heat at all or heats
insufficiently
- Warm air is supplied
Appliance does not
continuously
cool at all or cools
insufficiently
- Drops of water form
Water dripping from
between the door and
appliance
frame of the appliance
during operation
- Water drops from at the
condensate drain
connection point
ATTENTION: If the unit is disconnected from the electricity supply, follow the instructions given in chapter 3.2 Operational
safety.
For further description of possible problems and troubleshooting contact your supplier of the control and measurement system.
1 1 .
R e p a i r s , s p a r e p a r t s
All warranty and post-warranty repairs are performed by the manufacturer or an authorized service company. Service technician will
have an updated list of spare parts; you can also contact the manufacturer.
Symptoms
- Air in hot water heater
- Heating water temperature in the hot
water heater too low
- Heating water flow rate too low
- Maximum heater capacity too low
- Not found
- Air in water chiller
(only in CHW version)
- Cooling water temperature too low (only
in CHW version)
- Cooling water flow rate too low (only in
CHW version)
- Condensation unit is not running (only
in CHF version)
- Maximum chiller capacity too low
- Not found
- Condensate drain siphon trap is
insufficiently filled with water
- Condensate drain is blocked
- Damaged door seal
(the symptoms might include a whistling
sound caused by air flowing through the
gap)
- Condensate drain seal or pipes
damaged
- Not found
Possible causes
14

Troubleshooting

- Check heating water temperature
- Bleed air
- Check heating water temperature
- Check the condition of the sludge filter on the
heating water inlet; clean the filter
- No failure (incorrect design capacity - too low)
- Disconnect from power supply and contact
a service technician
- Air bleed the water chiller
- Check cooling water temperature
- Check the condition of the sludge filter on the
cooling water inlet; clean the filter
- Switch on the condensation unit
- No failure (incorrect design capacity - too low)
- Disconnect from power supply and contact
a service technician
- Disconnect from power supply and fill the
condensate drain siphon trap with water
- Disconnect from power supply and clean
the condensate drain including the siphon trap
and pipes
- Disconnect from power supply and check
the condition of the door seal
- If serious damage is discovered, contact a
service technician
- Disconnect from power supply and contact
a service technician
- Disconnect from power supply and contact
a service technician