HP StorageWorks XP10000 Site Preparation Manual page 35

Hide thumbs Also See for StorageWorks XP10000:
Table of Contents

Advertisement

Table 7. Floor load rating for service clearances (single rack)
Floor
load rating
2
(kg/m
)
500
450
400
350
300
Site requirements
Primary rack clearance notes and floor loading
The following notes apply to Figure 2
Note *1
(Figure
2): Clearance (a+b) depends on the floor load rating and
Required clearances for various floor load ratings are
clearance "c".
shown below.
Required clearance (a + b) mm
c = 0
c = 200
200
100
300
200
400
300
600
500
1000
800
Provide 100 mm of clearance on both sides of the disk array when the kick
plates are to be attached after the disk array is installed. When disk arrays
of the same type are to be installed adjacent to each other, clearance
between the arrays may be 100 mm.
Figure 2
(page 32)
the center of the disk array. The position may be off-center as long as the
cutout allows smooth entrance of an external cable (check the relation
between the positions of the cutout and the opening on the bottom plate of
the subsystem) and it is within the allowable range.
Additional notes:
• Decide actual clearances in consultation with the construction
specialist responsible for installation. They may vary depending on the
size and layout of the system and building conditions.
• When multiple disk arrays are arranged in a row, base your clearance
values on the requirements of the largest disk array.
• Generally, clearances ("c") should be as large as allowable.
(page 32)
Clearance (c) mm
c = 400
0.00
100
300
400
700
shows cutout dimensions. Position the floor cutout in
and Figure 3
(page
c = 600
c = 1000
0.00
0.00
100
0.00
200
100
400
200
600
500
33).
35