HP StorageWorks XP10000 Site Preparation Manual page 33

Hide thumbs Also See for StorageWorks XP10000:
Table of Contents

Advertisement

minimum side
clearance = 100 mm
Site requirements
Calculating clearances
See
Figure
3. The total floor clearance required for the disk array includes:
• The actual space required by the equipment.
• Service clearance — the floor space required to access the disk array.
Never use this space for storage.
• Additional space required to properly distribute the equipment weight
on your computer room's raised floor. The amount of additional space
required depends on your floor load rating.
Rear
Primary
a
Rack
Front
c
Figure 3. Primary rack clearance dimensions
rear
service
clearance
1000 mm
b
front
service
clearance
1000 mm
33