1. If the product is in Standby mode, proceed to step 3. If the product is in
Measurement mode, manual sampling is prevented.
2. Press the red Stop button to stop the measurement process. The display reads
"OIL DRAINING". If there is oil in the headspace, the draining process may take
several minutes. The product returns to Standby mode.
3. When the product is in Standby mode, remove the quick-connect body protector
by pulling the collar down.
4. Fit the male quick-connect fitting and valve assembly to the correct quick-connect
body on the base of the product as shown in Section 7.1. Ensure that the valve is
closed to prevent oil leakage.
5. Press the white Manual Sample button. The display reads "MANUAL DGA IN: 10s".
Subsequent presses of the white button are used to toggle through and select the
required oil circuit to sample. Once a circuit name is displayed, the timer
automatically counts down from 10 seconds, and if the white button is not
pressed again, the displayed circuit is selected for manual sampling.
product has to first switch oil circuits from the last measured circuit to the selected circuit, an "OIL
SWITCHING" notice displays.
6. An oil line purging process starts. The display reads "MANUAL DGA PURGING OIL
PRESS KEY WHEN DONE".
To ensure accurate results, oil must be adequately purged before sampling
begins. This brings fresh oil from the transformer to the manual oil sampling port.
Typically this means waiting approximately 5–10 minutes, but the recommended
wait time can vary depending on the installation (longer tubing and lower
temperatures can increase the purge duration). Consult with Technical Support.
7. Press the white Manual Sample button. The display reads "{oil circuit name}
MANUAL DGA TAKE OIL SAMPLE PRESS KEY WHEN DONE".
oil sampling process can begin.
8. Remove the Luer fitting cap, connect the oil sampling equipment e.g. syringe, and
perform the oil sampling according to your standard process and procedures.
9. When finished sampling, close the valve and disconnect the oil sampling
equipment.
10. Remove the male fitting and valve assembly, and replace the body protector
fitting on the quick-connect body.
11. Press the white Manual Sample button to return the product to Standby mode.
Note: If left in Manual Sampling mode, the product reverts to Standby mode after one hour.
Measurement then begins at the next scheduled measurement time.
To start a measurement immediately, press the blue Start button and then select
the oil circuit to measure.
To take a manual sample from another oil circuit, press the white Manual Sample button
again. If a measurement has started since the previous sample, first press the red Stop
button.
See Section 6.1 for example notifications from the LCD panel.
MA-003 – MULTITRANS User Guide – Rev 3.0