OSA 83RKSH & OSA 95RKSH
Reverse Cycle R410A Single Phase
Split System Outdoor Units
GENERAL
This OSA 83 and 95 Outdoor Units must be
installed in accordance with all national and
local safety codes.
Options
1. Vertical discharge grille.
2. Wall mounting brackets.
3. Anti-vibration mounts (rubber).
4. Soft starter kit
5. Drain connection adaptors - right angle.
INSTALLATION
Positioning
Refer to dimension diagram below for
minimum clearances. Position the unit so
that prevailing winds do not blow onto the
exhaust to slow the fan, and one unit does
not exhaust toward the inlet of another unit.
The optional vertical discharge grille can be
used to deflect prevailing winds and reduce
clearances.
Mount either free standing or on a wall using
the optional mounting brackets available.
Dimensions (mm)
100 MIN. CLEARANCE
2000 MIN. CLEARANCE *
660
OVERALL
72
25 DIA.
686 MTG CTR
174
DRAIN
12 DIA. HOLE+SLOT
HOLES
Free Standing :
Fasten the unit down to a firm flat horizontal
base using the four holes provided in the
mounting rails.
When the unit is being installed on a roof
it is recommended that the unit is installed
on a substantial structure with vibration
isolating springs or rubber mounts (optional
extra) beneath the unit. These items are not
supplied with the unit.
Wall Mounting Option:
Complete wall mounting instructions are
supplied with the optional wall mounting kit.
Drain
Four drain holes are provided in the base.
Three plastic bungs are supplied (loose)
should you want to direct the condensate
and/or rain water to one of the holes
provided. Drain connection adaptors (25/13)
are available as an optional extra.
25 DIA.
180
DRAIN
HOLES
1040
OVERALL
* 600 min with optional Vertical Discharge Grille
OSA 83/95 RKSH
PROJECTION
Not to Scale
Net Weight 85 kg
25 DIA.
ACCESS
ELECTRICAL
PANEL
CONDUIT
HOLES
REFRIG.
CONN'S
349
25
MTG CTR
395
OVERALL
Installation &
Maintenance
REFRIGERATION PIPING
General
The OSA 83/95 is shipped with a refrigerant
charge sufficient for a 10 m line length.
The matched indoor unit is shipped with a
holding charge of nitrogen. OSA 83/95 units
have shut-off service valves and swaged
assemblies. Two loose pipe extensions are
supplied to enable a choice of exit – side or
rear; both require brazing.
Recommended Pipe Sizes
Suction pipe :
16 or 19 mm OD
Liquid pipe :
10 mm OD
Line Lengths
The standard unit allows for a line length
up to 30 m. For line lengths between 30 m
and 40 m, refer to temperzone's
Split Systems Installation Guide (refer
www.temperzone.biz/Technical Support).
Refer also to Oil Charge overleaf.
Maximum line length when extended is 40m.
For line lengths in excess of 15 m use a
19 mm OD suction pipe size.
Height Separation Limits
Outdoor Unit above Indoor Unit : 16 m
Outdoor Unit below Indoor Unit : 16 m
Vertical Risers
If the outdoor unit is to be installed above
the indoor unit, then the suction riser should
be trapped at the bottom of the vertical
rise and then again at 5 m (maximum)
intervals. This is to ensure oil return to the
compressor. The trap to be a 'swan neck'
curve in the pipe, with no change in the pipe
size.
Piping
1. Use clean sealed refrigeration grade
piping and accessories designed
specifically for R410A.
2. Cut pipe with a pipe cutter ONLY.
3. Use long radius bends (2x pipe dia.).
4. Insulate the suction (gas) line and seal
all insulation joints.
5. Bi-flow type filter dryer may be fitted in
the liquid line.
6. Include a process point in the
interconnecting pipework.
7. Ensure open pipe ends are sealed until
the final connection is made.
8. Immediately before removing brazed
pipe connection's seal, reduce holding
charge between connection points and
service valves to atmospheric pressure.
Warning: Failure to do so may cause
injury.

Advertisement

loading

Summary of Contents for TemperZone OSA 83RKSH

  • Page 1 OSA 83RKSH & OSA 95RKSH Reverse Cycle R410A Single Phase Installation & Split System Outdoor Units Maintenance GENERAL REFRIGERATION PIPING Free Standing : This OSA 83 and 95 Outdoor Units must be Fasten the unit down to a firm flat horizontal...
  • Page 2 Charging Refer to temperzone for recommended 11. Check compressor compartment for oil thermostats. stains indicating refrigerant leaks. The unit is supplied with refrigerant HFC-410A (R410A) which is sufficient for 12. Touch up all outdoor unit paintwork It is recommended electricians run a spare up to 10 m of pipework between the indoor damage to prevent corrosion.