3.4 Liquid back control

■ Cooling mode
Discharge temperature
Tdis < Tc + 12˚C
Tdis > Tc + 16 ˚C
■ Heating mode
Discharge temperature
Tdis < Tc + 17˚C
Tdis > Tc + 18 ˚C
❇ The logic starts after 9min. on heating mode and 4min. on cooling mode from the compressor running.

3.5 Pressure switch

- The state of pressure sensing switch is normally on. It has small electric current from 220V AC. Never touch
the connecting terminal with hand nor short two wires directly.
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Indoor unit 's EEV
SH increasing control
Normal SH control
Outside unit 's EEV
SH increasing control
Normal SH control