Function

1. Basic control

1.1 Normal operation

Actuator
Compressor
Main EEV
4 way valve

1.2 Compressor control

Fuzzy control : Maintain evaporating temperature(Te) to be constant on cooling mode and condensing tem-
perature(Tc) on heating mode by Fuzzy control to ensure the stable system performance.
(Tc:47 ~ 51°C (117 ~ 124°F), Te:2 ~ 5°C (36 ~41°F))
(1) Cooling mode
Te can be set by initial DIP switch setting. (Standard, Long pipe)
(2) Heating mode
Tc can be set by initial DIP switch setting. (Standard, Long pipe)
Note: By setting DIP switch, Te and Tc are decided simultaneously.
Fuzzy control start
Set frequency
Stop
Fuzzy Control
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Cooling operation
Heating operation
Fuzzy control
Full open
OFF
Target
Fuzzy control
Fuzzy control
ON
(Linear Control)
(Linear Control)
(Linear Control)
Inverter linear control as cooling and heating load increasing
- 16 -
Stop state
Stop
Close
OFF
Inverter
Inverter
Inverter
Compressor
Compressor
Compressor
Cooling and heating load