Outside unit multi-v water mini series
Hide thumbs Also See for ARWN038GA2:

Advertisement

Internal Use Only
http://biz.lgservice.com
System
Outside Unit
R410A
SERVICE MANUAL R410A
MODEL : WATER MINI Series
CAUTION
Before Servicing the units, read the safety precautions in General SVC manual.
Only for authorized service personnel.

Advertisement

Table of Contents
loading

Summary of Contents for LG ARWN038GA2

  • Page 1 Internal Use Only http://biz.lgservice.com System Outside Unit R410A SERVICE MANUAL R410A MODEL : WATER MINI Series CAUTION Before Servicing the units, read the safety precautions in General SVC manual. Only for authorized service personnel.
  • Page 2: Table Of Contents

    External Appearance........................11 Nomenclature ..........................12 Part 2 Outside Units ......................... Part 3 Test Run .......................... Part 4 Trouble Shooting Guide ..................... - 2 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 3: Safety Precautions

    • There is risk of fire or electric shock. • Improper wiring or installation may cause fire or electric shock. - 3 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 4 LGE are used, fire or explosion may result. R410A R407C - 4 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 5 • There is risk of fire, electric shock, or product • There is risk of fire, electric shock, explosion, or damage. injury. - 5 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 6 • To avoid vibration or water leakage. • If the gas leaks and accumulates around the unit, an explosion may result. 90˚ - 6 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 7 • It may cause failure of appliance or accident. reduce the performance of the air conditioner or damage its parts. - 7 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 8 • Tear apart and throw away plastic packaging bags so that children may not play with them. If children play with a plastic bag which was not torn apart, they face the risk of suffocation. - 8 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 9 Do not insert hands or other objects through the air inlet or outlet while the air conditioner is plugged in. • There are sharp and moving parts that could cause personal injury. - 9 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 10: Part 1 General Information

    General Information 1. Model Names ..............11 1.1 Indoor Unit ...............11 2. External Appearance .............11 2.1 Outside Unit.............11 3. Nomenclature..............12 - 10 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 11: Model Names

    1Ø, 208/230V, 60Hz 038GA2 048GA2 053GA2 Heat Pump ARWN 2. External Appearance 2.1 Outside Unit • 1Ø ARWN038GA2 ARWN048GA2 ARWN053GA2 - 11 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 12: Nomenclature

    Cooling Only or Heat Pump N: Inverter and H/P Indicates that this is Water System Outside Unit using the R410A - 12 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 13: Part 2 Outside Units

    Part 2 Outside Unit - 13 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 14 Water Mini Series • Function ..................15 - 14 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 15 3.5 Pressure switch......................23 4. Other control ........................24 4.1 Initial setup .........................24 4.2 Vacuum Mode ......................26 4.3 Black Box Function ....................27 - 15 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 16: Basic Control

    Compressor Set frequency Stop Cooling and heating load Fuzzy Control Inverter linear control as cooling and heating load increasing - 16 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 17: Master And Slave Unit's Eev Control

    The degree of Superheat = Tsuction - Tevaporation Tsuction : temperature at suction pipe sensor (°C/°F) Tevaporation : evaporation temperature equivalent to low pressure (°C/°F) - 17 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 18: Special Control

    ■ Oil return operation time : 3min for running step ■ Starting condition:every 3hours operate ■ Oil return process ends if compressor protection control starts - 18 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 19 ■ Oil return operation time : 3min for running step ■ Starting condition:same as cooling mode ■ Oil return process ends if compressor protection control starts - 19 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 20: Stopping Operation

    (Before 15min. : Min. pulse) 4way valve After 60min. After 15min. Hot gas bypass valve (Before 15min. : ON) - 20 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 21: Protection Control

    3sec. ② Ps > 739kPa Normal control ❈ Frequency holding : frequency (or RPM) is not increasing (can decrease) - 21 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 22: Discharge Temperature Control

    15.5A or less 16A or more 25A or more Compressor Current 23/26A or less 23/26A or more 29A or more (Cooling/Heating) - 22 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 23: Liquid Back Control

    - The state of pressure sensing switch is normally on. It has small electric current from 220V AC. Never touch the connecting terminal with hand nor short two wires directly. - 23 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 24: Other Control

    Heat pump : Display 2 is default value Cooling only : no display Factory setting (25 is normal) Model Type - 24 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 25 Auto address process is finished. Every indoor unit displays its address on wired remote controller and the 7segment of main PCB is off. - 25 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 26: Vacuum Mode

    Main Lev, SC Lev OPEN IDU Lev OPEN Caution Outside unit operation stops during vacuum mode. Compressor can't operate. - 26 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 27: Black Box Function

    <Save EEP data> in LGMV ■ Saving process : Making Data ➠ Save EEP data ➠ data saving place select ➠ file save - 27 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 28: Test Run

    Part 3 PCB Setting and Test Run - 28 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 29: Part 3 Test Run

    • In case that the outside temperature is low, be sure to supply power 6hours before operation so that the heater is heated(insufficient heating may cause damage of the compressor.) - 29 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 30 • When CH05/53/11 ERROR occurs, check if auto-addressing has done and communication wiring is ok. - 30 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 31: Dip Switch Setting

    3.1 Location of setting Switch Main PCB SW01B SW02B (DIP S/W) (DIP S/W) 7 - Segment SW02V Auto addressing - 31 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 32 Normal mode display (If the dip switch is set incorrectly, it is not displayed.) Model type (Water Mini) ■ Mode code Model Code Unit(HP) Powersupply Ref. 1Ø, 208/230V R410A - 32 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 33 ■ If the dip switch is not set accurately, it can have excessive load on the product operation. Set the dip switch properly. - 33 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 34: Part 4 Trouble Shooting Guide

    Part 4 Trouble Shooting Guide - 34 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 35 2.1 Compressor ..................37 2.2 Electronic Expansion Valve...............38 2.3 Inverter IPM Checking Method ..............41 2.4 Other ......................42 3. Self-diagnosis function ..............43 - 35 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 36: The Phenomena From Main Component Failure

    • When CH05/53/11 ERROR occurs, check if auto-addressing has done and communication wiring is ok. - 36 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 37: Checking Method For Key Components

    (when measuring absolute values). Accurate measuring values cannot be obtained with a gen- eral movable tester (For analog and digital mode). - 37 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 38: Electronic Expansion Valve

    Full open% open EEV noise. 1350 pulses - If liquid refrigerant is in EEV, the noise is lower. pulse - 38 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 39 When the coil part is removed or assembled, be careful not to bend the pipe of the body. A part - 39 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 40 If estimated temperature is very low in comparison with suction temperature which is displayed at remote controller then the valve is not fully closed - 40 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 41: Inverter Ipm Checking Method

    W terminal : black (-) Open 28kΩ ± 10% ✽ Red (+) and black (-) are the measuring terminals of multi tester. - 41 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 42: Other

    LED 01Y turned off (wait 3min after main power OFF), otherwise it may cause electrical shock. - 42 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 43: Self-Diagnosis Function

    Compressor maintenance by outside unit high pressure Outside unit high pressure switch switch Flow rate insufficiency or flow switch trouble of out- side unit - 43 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 44 When the indoor uint control signal is not received from contrller and indoor unit the outside unit inverter controller - 44 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 45 Communication error between main MICOM and sub Communication error between MICOMs MICOM ■ Refer to the troubleshooting guide of service technical manual for each error. - 45 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 46: Troubleshooting Guide

    CN-PIPE2 : Pipe outlet temp sensor CN-PIPE1 : Pipe inlet temp sensor Measure the resistance of outlet pipe temp sensor. - 46 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 47 ❇ The PCB can differ from model to model. Check from the right source. Checking transmission cable connection status - 47 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 48 & the unit is stopped automatically. float (High position ➠ Open) Condensate water - 48 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 49 (Marked as CN-DPUMP) Float switch connector Float switch Housing (CN-FLOAT) [***] Standard of drain pipe head height / slope MAX 450 - 49 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 50 (-9V~+9V) then of communication terminal between IDU and ODU transmission from outside unit is normal - 50 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 51 With cableless remote controller: Turn off indoor unit, and then turn on by changing the operation mode. The error will disappear. - 51 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 52 - Replace the indoor unit PCB, and then make sure to perform Auto addressing and input the address of central control - 52 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 53 (Notice: The connection of motor connector to PCB should be done under no power supplying to PCB) - 53 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 54 Check inverter PCB assembly IPM normality Is inverter PCB assembly ➔ Replace inverter PCB assembly normal? Recheck power and installation condition - 54 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 55 * Inverter PCB & bridge diode wiring each terminal of compressor * Compressor wire connector connection * Measuring input voltage - 55 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 56 Check inverter PCB assembly IPM normality Is inverter PCB assembly normal? → Replace inverter PCB assembly Recheck power and installation condition - 56 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 57 Troubleshooting Guide * Measuring input voltage * Inverter PCB & bridge diode wiring - 57 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 58 Check inverter PCB assembly IPM normality Is inverter PCB assembly normal? ➔ Replace inverter PCB assembly Recheck power and installation condition - 58 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 59 Troubleshooting Guide * Measuring resistance between each terminal of compressor * Compressor wire connection - 59 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 60 Is inverter PCB assembly normal? Replace inverter PCB assembly Recheck power and installation condition * Measuring input voltage * Noise filter wiring - 60 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 61 Check inverter PCB assembly IPM normality Is inverter PCB assembly normal? → Replace inverter PCB assembly Recheck power and installation condition - 61 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 62 Troubleshooting Guide * Measuring resistance between each * Compressor wire connection terminal of compressor * Measuring input voltage - 62 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 63 Check another components Is there pipe and operation conditions (strainer etc.) clogging? / Take measures Replace strainer - 63 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 64 Replace sensor of high pressure value(Is it high actually)? Check indoor unit LEV Check indoor unit PCB Check in/outside installation condition - 64 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 65 (Notice: it is not full ice forming of strainer, in case that there is installation conditions not at inlet portion but at outlet portion) - 65 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 66 Is inverter PCB assembly normal? Recheck power and installation condition * Measuring input voltage * LGMV Part * Inverter PCB assembly - 66 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 67 10C = 362k : 25C= 200k : 50C= 82k : 100C= 18.5k Check the resistance Check the resistance inverter compressor of constant compressor discharge temperature discharge temperature sensor sensor - 67 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 68 After replacement of Replace corresponding outside unit main PCB pressure sensor is the system normal? High pressure sensor Low pressure sensor - 68 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 69 : 25C= 10k : 50C= 3.4k Sensor of piping temperature: 10C = 10k : 25C= 5k : 50C= 1.8k - 69 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 70 130% of outdoor unit same as the data of LGMV? unit capacity at LGMV? Adjust the capacity of indoor and outdoor unit - 70 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 71 * The method of checking MAIN PCB and inverter compressor PCB (If normal, transmission LED blinks) Transmission connector & LED in MAIN PCB Transmission connector & LED in inverter compressor PCB - 71 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 72 In case that only transmission PCB is replaced above process is not needed - 72 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 73 * Inverter EEPROM inserting point EEPROM enlarged picture * Right inserting direction of inverter EEPROM ❊ Note : Replace after power off - 73 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 74 Is inverter PCB assembly Check inverter PCB assembly IPM normality normal? → Replace inverter PCB assembly Recheck power and installation condition - 74 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 75 Inverter PCB assembly/Wiring power to inverter PCB on Noise filter Inverter PCB assembly power Noise filter power connection connection - 75 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 76 Replace inverter PCB assembly assembly normal? Recheck power and installing condition Measuring input voltage Inverter PCB & Bridge Diode wiring - 76 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 77 Reset after checking EEPROM assemble condition condition normal? Replace EEPROM with 24C16 Is EEPROM 24C16? Recheck power and installation condition - 77 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 78 Air temperature sensor: 10°C = 20.7kΩ : 25°C = 10kΩ : 50°C= 3.4kΩ Pipe temperature sensor: 10°C = 10kΩ : 25°C = 5kΩ : 50°C= 1.8kΩ - 78 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 79 If the same error is occurred in mode, is the same error near future replace 4way valve occurred again? Replace 4 way valve***** - 79 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 80 ➃ If there is a unit in which the difference is not increased then the 4way valve of that unit is defective - 80 - Copyright ©2013 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 81 APRIL, 2013 P/NO : MFL67101202...