PREMIER QUATRO ZT-TSRI Installation Manual
4.3.2 Master-Slave Configuration
In an installation, we will configure only one of the repeaters as a Master, which will be the
one that will communicate with the panel. All other devices will be Slaves and will be
managed by the Master.
To configure a repeater as a Master:
Device Type: Master
IP Net Master: No need to configure anything.
TCP Port Master: Port to access this equipment (Default 20010)
To configure a repeater as a Slave:
Device Type: Slave
IP Net Master: Enter the Master's IP.
TCP Port Master: Master's port (Default 20010).
4.4 Repeater Configuration
We can make changes to the configuration from the display or from the webserver.
4.4.1 General Settings
Language: Choose language of the repeater.
Time in seconds for the display be disconnected: Time for the screen to go into idle
mode with no activity. 0 to 65,000 secs.
Zone filtering: The repeater allows you to filter zones and display only the ones
configured here. To determine which zones to supervise, the following formula must
be applied: To supervise Panel 2 Zones 1-44 = p2z1-44 / to supervise Panel 1 zones
20-50 = p1z20-50 etc.
Simple mode: By enabling it, the repeater will not display any maps or map device
icons.
Hide events not related to zones: Disables the display of events that are not
associated with zones.
4.4.2 Serial/IP Ports
Modbus panel number: The number of the panel to which the repeater is
connected.
Modbus baud rate: The communication speed of the Modbus port.
4.4.3 Sound
Enable Alarm Sound: Activate/deactivate the alarm tone of the repeater during
Alarms.
Enable Fault Sound: Activate/deactivate the alarm tone of the repeater during
Faults.
Centralised Mute: If it is ON, when the buzzer is muted in the control panel, or if any
equipment on the network is muted, the repeater will also silence.
Doc No: GLT-281-7-1
Issue: 1.1
Author: TE
Firmware Version: 2_0z3
8
DATE: 16/11/2016