Download Print this page

Ranger PM3000 Configuration Manual page 21

Power quality data logger

Advertisement

3ø 4w Y Hmnc 7day (PM3000 Default)
Hook
Up: 3-Phase 4-Wire Wye
Channel Functions
Input Channels
1 Van 0 to 480 Vac
2 Ia
0 to 3000 Aac (Rogowski)
3 Vbn 0 to 480 Vac
4 Ib
0 to 3000 Aac (Rogowski)
5 Vcn 0 to 480 Vac
6 Ic
0 to 3000 Aac (Rogowski)
Detailed (Math) Channels
1 RMS of Signal Van (Vac)
2 RMS of Signal Vbn (Vac)
3 RMS of Signal Vcn (Vac)
4 RMS of Signal Ia (Aac)
5 RMS of Signal Ib (Aac)
6 RMS of Signal Ic (Aac)
7 % THD Traditional of Signal Van (%)
8 % THD Traditional of Signal Vbn (%)
9 % THD Traditional of Signal Vcn (%)
10 Value all Harmonics of Signal Ia (Aac)
11 Value all Harmonics of Signal Ib (Aac)
12 Value all Harmonics of Signal Ic (Aac)
13-16 Unspecified
PM3000 Power Quality Analyzer Factory Configurations
General Setup Values
Storage Mode: Adaptive Store
Recording Duration: 7 Days
FIFO / Recycle mode: Off
Input Calibration
Setup Values
1 Van 480 Volts = 480.0
2 Ia
1000 Amps = 1000.0
3 Vbn 480 Volts = 480.0
4 Ib
1000 Amps = 1000.0
5 Vcn 480 Volts = 480.0
6 Ic
1000 Amps = 1000.0
Alarms: On
Alarm Values High Low
1
Vac
253.0 216.2
2
Vac
253.0 216.2
3
Vac
253.0 216.2
7
%
8.0
8
%
8.0
9
%
8.0
Off
Off
Off
21

Advertisement

loading

Related Products for Ranger PM3000

This manual is also suitable for:

Pm3000hf