Download Print this page

Ranger PM3000 Configuration Manual page 20

Power quality data logger

Advertisement

3ø 4w Y Flkr THD 7day
Hook
Up: 3-Phase 4-Wire Wye
Channel Functions
Input Channels
1 Van 0 to 480 Vac
2 Ia
0 to 3000 Aac (Rogowski)
3 Vbn 0 to 480 Vac
4 Ib
0 to 3000 Aac (Rogowski)
5 Vcn 0 to 480 Vac
6 Ic
0 to 3000 Aac (Rogowski)
Detailed (Math) Channels
1 RMS of Signal Van (Vac)
2 RMS of Signal Vbn (Vac)
3 RMS of Signal Vcn (Vac)
4 RMS of Signal Ia (Aac)
5 RMS of Signal Ib (Aac)
6 RMS of Signal Ic (Aac)
7 % THD Traditional of Signal Van (%)
8 % THD Traditional of Signal Vbn (%)
9 % THD Traditional of Signal Vcn (%)
10 Flicker short term Van 10 mins (Pst)
11 Flicker short term Vbn 10 mins (Pst)
12 Flicker short term Vcn 10 mins (Pst)
13 Flicker long term Van 2 hours (Plt)
14 Flicker long term Vbn 2 hours (Plt)
15 Flicker long term Vcn 2 hours (Plt)
16 AC Frequency (Hz)
PM3000 Power Quality Analyzer Factory Configurations
General Setup Values
Storage Mode: Adaptive Store
Recording Duration: 7 Days
FIFO / Recycle mode: Off
Input Calibration
Setup Values
1 Van 480 Volts = 480.0
2 Ia
1000 Amps = 1000.0
3 Vbn 480 Volts = 480.0
4 Ib
1000 Amps = 1000.0
5 Vcn 480 Volts = 480.0
6 Ic
1000 Amps = 1000.0
Alarms: On
Alarm Values High Low
1
Vac
253.0 216.2
2
Vac
253.0 216.2
3
Vac
253.0 216.2
7
%
8.0
8
%
8.0
9
%
8.0
10
Pst
1.00 Off
11
Pst
1.00 Off
12
Pst
1.00 Off
13
Plt
0.80 Off
14
Plt
0.80 Off
15
Plt
0.80 Off
16
Hz
50.50 49.50
Off
Off
Off
20