Download Print this page

Ranger PM3000 Configuration Manual page 11

Power quality data logger

Advertisement

3ø 3el 11kV Flkr 7day
Hook
Up: 3-Phase 3-Wire Delta 3el
Channel Functions
Input Channels
1 Vab 0 to 480 Vac
2 Ia
0 to 500 Aac (0-500 mV)
3 Vbc 0 to 480 Vac
4 Ib
0 to 500 Aac (0-500 mV)
5 Vca 0 to 480 Vac
6 Ic
0 to 500 Aac (0-500 mV)
Detailed (Math) Channels
1 RMS of Signal Vab (kV)
2 RMS of Signal Vbc (kV)
3 RMS of Signal Vca (kV)
4 RMS of Signal Ia (Aac)
5 RMS of Signal Ib (Aac)
6 RMS of Signal Ic (Aac)
7 Flicker sensation on Vab (Pfs)
8 Flicker sensation on Vbc (Pfs)
9 Flicker sensation on Vca (Pfs)
10 Flicker short term Vab 10 mins (Pst)
11 Flicker short term Vbc 10 mins (Pst)
12 Flicker short term Vca 10 mins (Pst)
13 Flicker long term Vab 2 hours (Plt)
14 Flicker long term Vbc 2 hours (Plt)
15 Flicker long term Vca 2 hours (Plt)
16 AC Frequency (Hz)
PM3000 Power Quality Analyzer Factory Configurations
General Setup Values
Storage Mode: Adaptive Store
Recording Duration: 7 Days
FIFO / Recycle mode: Off
Input Calibration
Setup Values
1 Vab 480 Volts = 48.00
2 Ia
500 mV = 5.000
3 Vbc 480 Volts = 48.00
4 Ib
500 mV = 5.000
5 Vca 480 Volts = 48.00
6 Ic
500 mV = 5.000
Alarms: On
Alarm Values High Low
1
kV
11.66 10.34
2
kV
11.66 10.34
3
kV
11.66 10.34
10
Pst
1.00 Off
11
Pst
1.00 Off
12
Pst
1.00 Off
13
Plt
0.80 Off
14
Plt
0.80 Off
15
Plt
0.80 Off
16
Hz
50.50 49.50
11

Advertisement

loading

Related Products for Ranger PM3000

This manual is also suitable for:

Pm3000hf