Download Print this page

Ranger PM3000 Configuration Manual page 12

Power quality data logger

Advertisement

3ø 3el 11kV THD Flkr 7day
Hook
Up: 3-Phase 3-Wire Delta 3el
Channel Functions
Input Channels
1 Vab 0 to 480 Vac
2 Ia
0 to 500 Aac (0-500 mV)
3 Vbc 0 to 480 Vac
4 Ib
0 to 500 Aac (0-500 mV)
5 Vca 0 to 480 Vac
6 Ic
0 to 500 Aac (0-500 mV)
Detailed (Math) Channels
1 RMS of Signal Vab (kV)
2 RMS of Signal Vbc (kV)
3 RMS of Signal Vca (kV)
4 RMS of Signal Ia (Aac)
5 RMS of Signal Ib (Aac)
6 RMS of Signal Ic (Aac)
7 % THD Traditional of Signal Vab (%)
8 % THD Traditional of Signal Vbc (%)
9 % THD Traditional of Signal Vca (%)
10 Flicker short term Vab 10 mins (Pst)
11 Flicker short term Vbc 10 mins (Pst)
12 Flicker short term Vca 10 mins (Pst)
13 Flicker long term Vab 2 hours (Plt)
14 Flicker long term Vbc 2 hours (Plt)
15 Flicker long term Vca 2 hours (Plt)
16 AC Frequency (Hz)
12
PM3000 Power Quality Analyzer Factory Configurations
General Setup Values
Storage Mode: Adaptive Store
Recording Duration: 7 Days
FIFO / Recycle mode: Off
Input Calibration
Setup Values
1 Vab 480 Volts = 48.00
2 Ia
500 mV = 5.000
3 Vbc 480 Volts = 48.00
4 Ib
500 mV = 5.000
5 Vca 480 Volts = 48.00
6 Ic
500 mV = 5.000
Alarms: On
Alarm Values High Low
1
kV
11.66 10.34
2
kV
11.66 10.34
3
kV
11.66 10.34
7
%
8.0
8
%
8.0
9
%
8.0
10
Pst
1.00 Off
11
Pst
1.00 Off
12
Pst
1.00 Off
13
Plt
0.80 Off
14
Plt
0.80 Off
15
Plt
0.80 Off
16
Hz
50.50 49.50
Off
Off
Off