For the purposes of programming
the UDS100, select option four,
'Telnet to Device'.
Connecting through port 9999,
the user will be connected to a
Telnet session.
15.
A Lantronix Device Universal
Server DOS screen will appear
prompting the user to press Enter
to go into Setup Mode. Press
<enter>.
The duration of programming
will be completed through the
DOS screen.
16.
At the 'Your Choice?' prompt,
Enter "0" then <enter> to go into
Server Configuration.
17.
At the IP Address prompt, Enter
the IP Address of the UDS100
then <enter>.
7-101002-00
18.
At the Gateway IP Address
prompt
a.
Hit enter immediately if no
gateway is required.
b.
Type 'Y', if a gateway is
used. If the user selects 'Y',
at the Gateway IP Addr
(000) prompt, enter the gate-
way address then <enter>.
19.
At the Netmask Number of Bits
for Host Part (0=default) (00)
prompt, enter 8,16 or 24 pending
the subnet mask class being used:
8 = Class C = subnet
255.255.255.0
16 = Class B = subnet
255.255.0.0
24 = Class A = subnet 255.0.0.0
20.
Change Telnet Config Password
(N), press <enter>.
The Change Setup Menu will
now re-appear.
21.
At the 'Your Choice ?' prompt,
enter "1" thenn <enter> in order
to go into the Channel 1 Configu-
ration.
22.
At the Baud Rate prompt, enter
9600 then <enter>.
23.
I/F Mode is not used, press
<enter>.
24.
At the Flow prompt, type 00 then
<enter> in order to disable Flow
Control.
25.
At Port No (10001), type, 3001
then <enter>.