Honeywell Access Systems
Problem/Message
When attempting to assign
an IP with DeviceInstaller,
the following message
appears: "No response
from device! Verify the IP ,
Hardware address and
Network Class. Please try
again."
No LEDs are illuminated.
The UDS100 will not power
up properly, and the LEDs
are flashing.
The UDS is not communi-
cating with the serial
device attached to the
UDS.
When attempting to enter
the setup mode on the
UDS via the serial cable,
there is no response.
7-101002-00
Reason
The cause is most likely
one of the following: The
Hardware address speci-
fied is incorrect. The IP
address being assigned is
not a valid IP for the logical
subnet.
The correct subnet mask
was not selected.
The unit or its power sup-
ply is damaged, or the unit
is not plugged into power
properly.
Various.
The most likely reason is
the wrong serial cable or
serial settings were cho-
sen.
The issue will most likely
be something covered in
the previous problem, or
possibly the Caps Lock is
on.
LANSRLU1
Solution
Double-check the speci-
fied parameters. Tip: An IP
address cannot be
assigned to a UDS
through a router.
Try plugging the UDS into
another outlet. If this does
not fix the problem, con-
tact the dealer or Lantronix
Technical Support for a
replacement.
Consult the LEDs section
in the Introduction chapter
or the Quick Start guide for
the LED flashing sequence
patterns. Call Lantronix
Technical Support if the
blinking pattern indicates a
critical error.
Make sure to use the cor-
rect serial cable. The UDS
serial port is just like a
modem serial port (DCE).
The serial settings for the
serial device and the UDS
must match. The default
serial settings for the UDS
are RS232, 9600 Baud, 8
Character Bits, No Parity, 1
Stop Bit, No Flow Control.
Double check everything
in the problem addressed
above. Confirm that Caps
Lock is not on.
13