2. When the climate system selection has been con-
firmed, the curve number is marked.
3. Press the OK button to access the setting mode
4. Select a new curve. The curves are numbered from
0 to 15, the greater the number, the steeper the
slope and the greater the supply temperature. Curve
0 means that
own curve
5. Press the OK button to exit the setting.
To read off a curve:
1. Turn the control knob so that the ring on the shaft
with the outdoor temperature is marked.
2. Press the OK button.
3. Follow the grey line up to the curve and out to the
left to read off the value for the supply temperature
at the selected outdoor temperature.
4. You can now select to take read outs for different
outdoor temperatures by turning the control knob
to the right or left and read off the corresponding
flow temperature.
5. Press the OK or Back button to exit read off mode.
TIP
Wait 24 hours before making a new setting, so
that the room temperature has time to stabilise.
If it is cold outdoors and the room temperature
is too low, increase the curve slope by one incre-
ment.
If it is cold outdoors and the room temperature
is too high, lower the curve slope by one incre-
ment.
If it is warm outdoors and the room temperature
is too low, increase the curve offset by one incre-
ment.
If it is warm outdoors and the room temperature
is too high, lower the curve offset by one incre-
ment.
NIBE™ F1255
(menu 1.9.7) is used.
Chapter 6 |
Commissioning and adjusting