PRODUCT DESIGN
CIRCULATING AIR AND FILTERS
DUCTWORK - AIR FLOW
Duct systems and register sizes must be properly designed
for the C.F.M. and external static pressure rating of the fur-
nace. Ductwork should be designed in accordance with the
recommended methods of "Air Conditioning Contractors of
America" manual D.
A duct system should be installed in accordance with Stan-
dards of the National Board of Fire Underwriters for the In-
stallation of Air Conditioning, Warm Air Heating and Venti-
lating Systems, Pamphlets No. 90A and 90B.
A return air filter is not supplied with the furnace. The in-
staller must supply a means of filtering all of the return air.
Filter(s) shall comply with UL900 or CAN/ULC-S111 Stan-
dards. If the furnace is installed without filters, the warranty
will be voided.
The following two charts show the bottom and side return
filter sizes available for each size furnace. Larger sizes are
also acceptable.
SIDE RETURN
Cabinet
Nominal
Approx.
Width
Filter
Flow Area
(In.)
Size (In.)
(In.)
All
16x25x1
400
Refer to Minimum Filter Area tables to determine filter area
requirement. NOTE: Filters can also be installed elsewhere
in the duct system such as a central return.
AMV8, ADV8, AMH8, AMS8, ADS8, DDS8, DMS8,
DHS8, GMS8, GDH8, GDS8, GHS8, GME8, GMH8,
MINIMUM FILTER SIZES
FURNACE INPUT
45M
68M
90M
115M
135M
45M
68M
90M
115M
135M
PERMANENT NOMINAL 600 F.M. FACE VELOCITY
DISPOSABLE NOMINAL 300 F.M. FACE VELOCITY
BOTTOM RETURN
Cabinet
Nominal
Width
Filter
Flow Area
(In.)
Size (In.)
14"
14X25X1
17-1/2
14X25X1
21
16x25x1
24-1/2
20X25X1
GMV8
FILTER SIZE
TYPE
2
permanent
160 in
2
permanent
241 in
2
permanent
320 in
2
permanent
400 in
2
permanent
370 in
2
disposable
320 in
2
disposable
483 in
2
disposable
640 in
2
disposable
800 in
2
disposable
738 in
AMV9, ACV9, GMV9, GCV9, GMV95
0453_XA
0703_XA
0704_XA
0904_XA
0905_XA
1155_XA
*Minimum filter area dictated by heating airflow requirement.
Disposable Minimum Filter Area (in
[Based on a 300 ft/min filter face velocity]
Approx.
(In.)
350
0453_XA
350
400
0703_XA
500
0704_XA
0904_XA
0905_XA
115_XA
COOLING AIRFLOW REQUIREMENT (CFM)
600
800
1000
1200
1400
376*
384
480
576
---
---
564*
564*
564*
672
---
---
564*
564*
672
---
---
752*
752*
752*
---
---
---
752*
752*
---
---
---
940*
940*
COOLING AIRFLOW REQUIREMENT (CFM)
600
800
1000
1200
1400
188*
192
240
288
---
282*
282*
282*
336
---
---
260*
260*
336
---
---
376*
376*
376*
---
---
---
376*
376*
---
---
---
470*
470*
1600
2000
---
---
---
---
768
---
768
---
768
800
940*
800
)
2
1600
2000
---
---
---
---
---
384
---
384
---
384
480
470*
480