Goodman ACS series Service Instructions Manual page 109

80%, 90%, 95%
Table of Contents

Advertisement

SERVICING
THERMOSTAT CONTINUOUS FAN INPUT(S):
R, G
First, low voltage readings are measured with the 16-pin wire
harness disconnected from the motor. A diagram of the har-
ness and pin locations is provided below. Voltage measure-
ment is AC or DC as specified in the chart below under the
(Volts) column. Set your voltage meter to the proper AC or
DC reading as requested below.
Thermostat Input(s): R, G
Description
Pin
Com, C1
1
W/W1
2
Com, C2
3
(4)
4
Delay
(4)
5
Cool
Y1
6
(4)
7
Adjust
(3)
8
Out -
O
9
(2)
10
Bk/PWM
(4)
11
Heat
R
12
EM/W2
13
Y/Y2
14
(1)
15
G
(3)
16
Out +
(1) This input must be active for motor to operate.
(2) 0 VAC indicates humidistat is calling for dehumidification.
(3) These two pins form an output circuit that powers the CFM LED on the ignition control or interface board.
(4) Dipswitch settings determine measure voltage.
(5) Voltage is measured with 16-wire harness disconnected from motor. Voltage measurement is AC or DC as specified in the chart.
VARIABLE SPEED (ECM) MOTOR TEST
(Fan Only Call)
(5)
Signal Indicates
Volts
0 VAC
Common
0 VAC
W1 = OFF
0 VAC
Common
0 VAC
Delay Tap = A
≥ 10 VDC
Delay Tap = B
≤ -10 VDC
Delay Tap = C
24 VAC
Delay Tap = D
0 VAC
Cool Tap = A
≥ 10 VDC
Cool Tap = B
≤ -10 VDC
Cool Tap = C
24 VAC
Cool Tap = D
0 VAC
Y1 = OFF
0 VAC
Adjust Tap = A
≥ 10 VDC
Adjust Tap = B
≤ -10 VDC
Adjust Tap = C
24 VAC
Adjust Tap = D
0 VDC
Common
0 VAC
O = OFF
24 VAC
No Dehumidification
0 VAC
Heat Tap = A
≥ 10 VDC
Heat Tap = B
≤ -10 VDC
Heat Tap = C
24 VAC
Heat Tap = D
24 VAC
R = ON
0 VAC
EM/W2 = OFF
0 VAC
Y/Y2 = OFF
≥ 13 VAC
G = ON
0-3.5 VDC
CFM LED
ECM Motor Not Coming On
In order for the continous fan speed to operate, the inte-
grated control board has to receive (G) signal from the ther-
mostat. Turn the thermostat to the Fan On position. If the
fan will not run, verify 24 volts on the integrated control boards
low voltage terminal strip at (C) and (R) with your volt meter.
If you have 24 volts, place a jumper wire between the (R) and
(G) terminal on the control board. If the motor now operates
then you have a problem in the thermostat cable from the
thermostat or with the thermostat.
Unplug the 16-pin harness from the ECM motor. Set volt
meter to read AC volts. Place your voltage meter on Pin
1(Common) and Pin 12 (R), you should read 24 AC volts.
Finally, check between Pin 1(Common) and Pin 15 (G), you
should read 13 AC Volts.
You MUST have all of these low voltage readings before the
ECM motor will come on. If you DO NOT have these read-
ings you may have a 16-pin wire harness or integrated con-
trol board problem.
Make sure you have high voltage at the 5-pin connector go-
ing to the motor as discussed earlier.
We highly recommend using the GE TECMate PRO™ model
ECM motor tester. This low cost test instrument will verify
whether the motor itself is good.
8
ADJUST +/-
Y 1
COOL
COMMON 2
COMMON 1
CONTROL CONNECTOR
"Motor Half"
(Viewed from connector end)
16
OUT +
EM HT/W2
24VAC (R)
BK/Pwm (Speed)
O (Rev Valve)
109