1 - CODE REQUIREMENTS
1.1 - Regulations and
guidelines
- The installation must conform to the
requirements of the authority having
jurisdiction or, in the absence of such
requirements, to:
- the latest edition of the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 and or CAN/
CSA B149.1, Natural Gas and Propane
Installation Code;
- the latest edition of the National Electric
Code ANSI/NFPA 70 and or Canadian
Electrical Code Part 1 CSA C22.1.
- Where required by the authority having
jurisdiction, the installation must conform
to the Standard for Controls and Safety
Devices for Automatically Fired Boilers,
ANSI/ASME CSD-1
NOTICE!
Install CO detectors per local regulations.
NOTICE!
This appliance meets the safety and other
performance requirements as specified in
ANSI Z21.13 standard.
NOTICE!
Per DOE mandate, the operator control
incorporates an automatic means (outdoor
reset) of adjusting the boiler water
temperature for hot water heating. The boiler
must operate with the automatic means
enabled.
NOTICE!
In accordance with Section 325 (f)(3) of the
energy policy and conservation Act, this boiler
is equipped with a feature that saves energy
by reducing the boiler water temperature as
the heating load decreases.