Network Troubleshooting; System Troubleshooting; Fault Recall Sequence - Intertek MVM97 Series Installation Instructions Manual

Type fsp category iv direct or non direct vent air furnace
Table of Contents

Advertisement

D
IAGNOSTICS
Accessing the furnace's diagnostics menu provides ready access to the last ten faults detected by the furnace. Faults are stored
most recent to least recent. Any consecutively repeated fault is stored a maximum of three times. Example: A clogged return air
filter causes the furnace limit to trip repeatedly. The control will only store this fault the first three consecutive times the fault
occurs.
NOTE: It is highly recommended that the fault history be cleared when performing maintenance or servicing the furnace.
N
ETWORK TROUBLESHOOTING
The indoor control is equipped with a bank of three DIP switches that provide biasing and termination functions for the commu-
nications transmission lines. The outdoor control in the communicating compatible unit is equipped with a bank of two DIP
switches that provide termination functions for the communications transmission lines. Communications errors will result if
these switches are not correctly set. Note that the ON position is the correct position for all bias and pull up/pull down DIP
switches.
The ComfortNet™ system is a fully communicating system, and thus, constitutes a network. Occasionally the need to troubleshoot
the network may arise. The furnace control board has some on-board tools that may be used to troubleshoot the network. These
tools are: red communications LED, green receive (Rx) LED, and learn button.
Red communications LED – Indicates the status of the network. The table below indicates the LED status and the
corresponding potential problem.
Green receive LED – Indicates network traffic. The table below indicates the LED status and the corresponding potential
problem.
Learn button – Used to reset the network. Depress the button for approximately 2 seconds to reset the network.
S
T
YSTEM
ROUBLESHOOTING
NOTE: Refer to the instructions accompanying the ComfortNet compatible outdoor AC/HP unit for troubleshooting information.
Refer to the Troubleshooting Codes for a listing of possible furnace error codes, possible causes and corrective actions.
F
R
S
AULT
ECALL
EQUENCE
Only allowed in standby mode while display is showing ON.
Hold fault recall push-button for 2-5 seconds (until display is blank) and then release.
Display will then be blank for 2 seconds before displaying faults stored in history.
All faults are displayed one time, from most recent to least recent.
A Maximum of 3 consecutive faults of the same type will be logged.
Each error is displayed for 2 seconds, with a blank screen for 1 second in between.
When all errors have been displayed, the display returns to ON.
LED
LED Status
Off
Red
2 Flashes
Communications
LED
Rapid Flashing •   Normal network traffic
On Solid
Green
Receive
LED
Indication
•   Normal condition
•   None
•   Out-of-box reset
•   Control power up
•   Learn button depressed
•   Control is "talking" on
network as expected
•   Data 1/ Data 2 miss-
•   Data 1 and data 2 wires reversed
wire
at furnace, thermostat or
communicating compatible
outdoor AC/HP
•   Short between data 1 and
data 2 wires.
•   Short between data 1 or
data 2 wires and R
(24VAC) or C (24VAC
common).
Possible Causes
Corrective Action(s)
•   None
•   None
•   None
•  Check communications
wiring (data 1/ data 2
wires).
•  Check wire connections at
terminal block
•  Check data 1/ data 2
voltages.
49
Notes & Cautions
•   None
•   None
•   None
•  Turn power OFF prior to
repair.
•   Verify wires at terminal
blocks are securely twisted
together prior to inserting
into terminal block.
•  Verify data 1 and data
voltages as described above

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cvm97 series

Table of Contents