Propane Gas Tanks And Piping - Intertek MVM97 Series Installation Instructions Manual

Type fsp category iv direct or non direct vent air furnace
Table of Contents

Advertisement

P
G
T
P
ROPANE
AS
ANKS AND
A gas detecting warning system is the only reliable way to detect a
propane gas leak. Rust can reduce the level of odorant in propane
gas. Do not rely on your sense of smell. Contact a local propane
gas supplier about installing a gas detecting warning system. If
the presence of gas is suspected, follow the instructions listed in
the Safety Precautions section of this manual.
All propane gas equipment must conform to the safety standards
of the National Board of Fire Underwriters, NBFU Manual 58.
CANADA: National Standard of Canada, Natural Gas and Pro-
pane Installation Code (NSCNGPIC) CSA B149.1—2010.
For satisfactory operation, propane gas pressure must be 10" WC + .5" WC at the furnace manifold with all gas appliances in
operation. Maintaining proper gas pressure depends on three main factors:
1. Vaporization rate, depending on temperature of the liquid, and "wetted surface" area of the container or containers.
2. Proper pressure regulation. (Two-stage regulation is recommended for both cost and efficiency).
3. Pressure drop in lines between regulators, and between second stage regulator and the appliance. Pipe size will depend on
length of pipe run and total load of all appliances.
Complete information regarding tank sizing for vaporization, recommended
regulator settings, and pipe sizing is available from most regulator manu-
facturers and propane gas suppliers.
Since propane gas will quickly dissolve white lead and most standard com-
mercial compounds, special pipe dope must be used. Pipe dope used on
propane gas installations must be approved for use with propane
gas.
Refer to the Figure 39 for typical propane gas installations and piping.
Sizing Between First and Second Stage Regulator*
Maximum Propane Capacities listed are based on 2 psig pressure drop at 10 psig setting.
Capacities in 1,000 BTU/hour.
Pipe or
Tubing Size, O.D. Type L
Tubing
Length
Feet
3/8"
1/2"
5/8"
10
730
1,700
3,200
20
500
1,100
220
30
400
920
2,000
40
370
850
1,700
50
330
770
1,500
60
300
700
1,300
80
260
610
1,200
100
220
540
1,000
125
200
490
900
150
190
430
830
175
170
400
780
200
160
380
730
To convert to capacities at 15 psig settings - multiply by 1.130
To convert to capacities at 5 psig settings - multiply by 0.879
Propane Gas Piping Chart I
IPING
Nominal Pipe Size
Schedule 40
3/4"
7/8"
1/2"
5,300
8,300
3,200
3,700
5,800
2,200
2,900
4,700
1,800
2,700
4,100
1,600
2,400
3,700
1,500
2,200
3,300
1,300
1,900
2,900
1,200
1,700
2,600
1,000
1,400
2,300
900
1,300
2,100
830
1,200
1,900
770
1,100
1,800
720
I
F THE GAS FURNACE IS INSTALLED IN A BASEMENT
AREA OR CONFINED SPACE
CONTACT A PROPANE SUPPLIER TO INSTALL A GAS DETECTING WARNING
DEVICE IN CASE OF A GAS LEAK
S
INCE PROPANE GAS IS HEAVIER THAN AIR
SETTLE IN ANY LOW AREAS OR CONFINED SPACES
P
ROPANE GAS ODORANT MAY FADE
EXCEPT WITH A WARNING DEVICE
First Stage
Regulator
Sizing Between Second or Second Stage Regulator & Appliance*
Maximum Propane Capacities listed are based on 1/2" W.C. pressure drop at 11" W.C. setting.
Capacities in 1,000 BTU/hour.
Pipe or
Tubing
Length
3/4"
Feet
3/8"
7,500
10
39
4,200
20
26
4,000
30
21
3,700
40
19
3,400
50
18
3,100
60
16
2,600
80
13
2,300
100
11
2,100
125
10
1,900
150
9
1,700
200
8
1,500
250
8
*Data in accordance with NFPA pamphlet No. 54
WARNING
,
IT IS STRONGLY RECOMMENDED TO
.
,
ANY LEAKING GAS CAN
,
MAKING THE GAS UNDETECTABLE
.
5 to 15 PSIG
(20 PSIG Max.)
200 PSIG
Maximum
Propane Gas Installation (Typ.)
Figure 39
Tubing Size, O.D. Type L
1/2"
5/8"
3/4"
7/8"
1/2"
92
199
329
501
275
62
131
216
346
189
50
107
181
277
152
41
90
145
233
129
37
79
131
198
114
35
72
1,211
187
103
29
62
104
155
89
26
55
90
138
78
24
48
81
122
69
21
43
72
109
63
19
39
66
100
54
17
36
60
93
48
Propane Gas Piping Chart II
,
AN EXCAVATED
.
Continuous
11" W.C.
Second Stage
Regulator
Nominal Pipe Size
Schedule 40
3/4"
1"
1-1/4" 1-1/2"
567
1,071 2,205
3,307
393
732
1,496
2,299
315
590
1,212
1,858
267
504
1,039
1,559
237
448
913
1,417
217
409
834
1,275
185
346
724
1,066
162
307
630
976
146
275
567
866
132
252
511
787
112
209
439
665
100
185
390
590