4.

Installation

4.1

Location

The 824 is designed for installation in climate controlled
living spaces. Place the unit in a central location with good
circulation.
For proper temperature sensing, avoid exposing the 824 to
heat radiated from lamps, sun light, fireplaces or any other
radiant heat source.
Avoid locations close to windows, behind doors or alcoves
with poor air circulation, adjoining outside walls, or doors
that lead to the outside.
Select a location that prevents the 824 from being directly
exposed to air currents from supply registers or ceiling fans.
Mount the Control on a section of interior wall that does not
contain hot or cold water pipes or duct work.
Important: The 824 Control utilizes a 4.3" color touch
screen. This screen generates heat which is vented out
the top of the Control utilizing natural convection. If an air
source is directed at or from above, heat from the screen
can be trapped within the Control and can cause the indoor
temperature to be biased. (Refer to Figure 1 on page 4.)
FIGure 1. PLACeMeNT OF THe 824
Correct
Placement
2 FEET
Optimum
Zone
5 FEET
Incorrect
Placement
Heat from the screen may be trapped
within the body of the Control by an
external top-down airflow source, such
as a ceiling fan.
The onboard thermistor may be biased
by this heat causing the displayed
indoor temperature to be elevated.
4
Natural heat
dissipation
from the
Touch Screen
Onboard
Thermistor
Ceiling Fan
4.2

Network Connections

To take advantage of the full range of features on the 824
Control, it should be connected to the Internet. This is
possible using either a wireless or a wired connection.
Wireless Connections
If the 824 Control will be connected to the Internet using the
built-in wireless feature, choose a mounting location that
ensures adequate signal strength from the Internet router.
Tips to Help Maximize Signal Strength:
— Do not mount the Control more than 30 feet from the
wireless router
— There should be no more than three interior walls
between the Control and the router.
— Do not mount the Control in areas where
electromagnetic emissions from other devices,
appliances or wiring can interfere with the Control's
communication. (i.e. wireless
systems, wireless Internet cameras).
— Do not mount the Control in recessed areas,
near metal objects, or near structures. (i.e. doors,
appliances, entertainment centers or shelving units).
— Do not mount the Control closer than 2 inches to any
pipes, duct work, or other metal obstructions.
— Do not have metal obstructions, concrete or brick
walls between the Control and the router.
Incorrect
Refer to the 824 User Guide for additional information on
Placement
connecting the 824 to the Internet.
Wired Connections
The 824 Control may be connected to the Internet using its
Heat from the screen may be trapped
within the body of the Control by an
built-in RJ-45 connector. When using a wired connection,
external top-down airflow source, such
verify that a CAT 5 or better Ethernet cable with a male
as a ceiling fan.
RJ-45 connector is present from the router to the Control.
4.3

Mounting

Follow these steps to mount the 824 Control to the wall.
1. Turn OFF all power to heating and cooling equipment.
The onboard thermistor may be biased
2. If an existing thermostat is being replaced:
by this heat causing the displayed
indoor temperature to be elevated.
a. Remove the existing thermostat from the wall.
b. Record color and terminal marking of each wire.
c. Disconnect the wires from the existing thermostat
being careful not to allow them to fall back into
the wall.
3. Carefully pry the Sub-base away from the 824 Control
using a small flat-blade screwdriver. Note that the
tight fit is normal and ensures that the Control is held
securely to the Sub-base when mounted on the wall.
4. Route the wires through the opening on the Sub-base.
5. If using a wired Internet connection, route the Ethernet
cable through the opening.
phones,
Ceiling Fan
18-HD72D1-6
security

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents

Save PDF