TCONT802AS32DA Touch Screen and
TCONT803AS32DA Touch Screen with
Dehumidification Control Comfort Controls
18-HD25D19-3
APPLICATION
The TCONT802AS32DA and TCONT803AS32DA Touch Screen Comfort Controls provide electronic control of 24 Vac
heating and cooling systems. See Table 1 for a general description.
Table 1. TCONT802AS32DA and TCONT803AS32DA Comfort Control Description.
Power Method
24 Vac common
Automatic or
wire
manual selectable
MERCURY NOTICE
If this control is replacing a control that contains
mercury in a sealed tube, do not place your old
control in the trash. Dispose of properly.
Contact your local waste management authority
for instructions regarding recycling and the
proper disposal of the old control.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
the instructions can damage the product or cause
a hazardous condition.
2. Installer must be a trained, experienced service
technician.
3. After completing installation, use these instructions
to check out the product operation.
U.S. Pat. No. 6595430, D509151, and Other Patents Pending
Changeover
System Selection
Heat-Off-Cool-
Auto (Em. Heat
for heat pumps)
INSTALLATION INSTRUCTIONS
Fan Selection
On-Auto-Circ
Selecting Location
Install the comfort control about 5 ft. (1.5m) above the
floor in an area with good air circulation at average
temperature. See Fig. 1.
NO
NO
Fig. 1. Selecting comfort control location.
Comments
System and Fan selection
vary based on system type
System and Fan selection
vary based on System type.
Humidity sensor to control
dehumidification.
NO
YES
5 FEET
[1.5 METERS]
69-1790-3
M19925

Advertisement

Table of Contents
loading

Summary of Contents for Trane TCONT802AS32DA

  • Page 1 TCONT802AS32DA Touch Screen and TCONT803AS32DA Touch Screen with Dehumidification Control Comfort Controls 18-HD25D19-3 INSTALLATION INSTRUCTIONS APPLICATION The TCONT802AS32DA and TCONT803AS32DA Touch Screen Comfort Controls provide electronic control of 24 Vac heating and cooling systems. See Table 1 for a general description. Table 1.
  • Page 2: Wiring

    TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION Do not install the comfort control where it can be affected 3. Securely tighten each screw. 4. Push excess wire back into the hole. — Drafts or dead spots behind doors and in corners. 5.
  • Page 3: Hookups

    TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION HEAT/COOL HEAT/COOL VARIABLE SPEED TWO-STAGE HANDLER FURNACE/VARIABLE SPEED AIR HANDLER INDOOR INDOOR OUTDOOR OUTDOOR COOLING UNIT COOLING UNIT O.D. SECTION O.D. SECTION (SINGLE STAGE) (TWO STAGE) (3 PH TO POWER SUPPLY (3 PH TO POWER SUPPLY ONLY)
  • Page 4 TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION HEAT PUMP I-PF PM-A SUPPL. HTR. CONTROL BOX HANDLER REQ. ODT-1 3 PH TO POWER SUPPLY PER LOCAL ODT-2 CODES AND AS DEFINED IN FIELD WIRING TABLE INDOOR OUTDOOR HEAT PUMP O.D.
  • Page 5 TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION HEAT PUMP VARIABLE SPEED AIR HANDLER INDOOR OUTDOOR 16 SEER HEAT PUMP O.D. SECTION X2/BK BR(T) (TWO STEP) (3 PH TO POWER SUPPLY ONLY) PER LOCAL CODES FACTORY INSTALLED JUMPER. OUTDOOR REMOTE SENSOR. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
  • Page 6 TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION HEAT PUMP VARIABLE SPEED TWO STAGE FURNACE INDOOR OUTDOOR HEAT PUMP BR/X2 BR(T) O.D. SECTION OR BK (SINGLE STAGE) (3 PH TO POWER SUPPLY ONLY) PER LOCAL CODES FACTORY INSTALLED JUMPER. OUTDOOR REMOTE SENSOR.
  • Page 7 TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION HEAT PUMP VARIABLE SPEED TWO STAGE FURNACE INDOOR OUTDOOR HEAT PUMP X2/BK BR(T) O.D. SECTION (TWO STAGE) (3 PH TO POWER SUPPLY ONLY) PER LOCAL CODES FACTORY INSTALLED JUMPER. OUTDOOR REMOTE SENSOR. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
  • Page 8 TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION HEAT PUMP VARIABLE SPEED TWO STAGE FURNACE INDOOR OUTDOOR 16 SEER X2/BK BR(T) HEAT PUMP O.D. SECTION (TWO STEP) (3 PH TO POWER SUPPLY ONLY) PER LOCAL CODES FACTORY INSTALLED JUMPER. OUTDOOR REMOTE SENSOR.
  • Page 9 TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION Mounting the Comfort Control This comfort control is designed to automatically keep the current time and day in memory for up to ten years under 1. Align the terminal screw blocks with the pins on the normal use once the calendar is set.
  • Page 10: System And Fan Settings

    TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION OPERATION TO C System and Fan Settings The System default setting is Heat and the Fan default EQUIPMENT setting is Auto. MONITOR TO R SYSTEM SETTINGS M22646 Heat: controls heating system. Off: heating and cooling are off.
  • Page 11: Installer Setup

    TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION INSTALLER SETUP The comfort control works with many different system 4. Release the two blank keys when the screen on the types. To operate correctly, the comfort control must be comfort control matches the screen below. set up to operate the installed heating and/or cooling system.
  • Page 12: Installer Setup Menu

    TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION IMPORTANT The Installer Setup Menu (Table 4) shows all the available options. These options customize themselves as you make selections to the Installer Setup. Therefore, not all Installer Setup Selections are shown or are avail- able to change.
  • Page 13: Factory Setting

    TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION Table 4. Installer Setup Menu. (Continued) Factory Setting Other Choices Installer Setup Select Number Option Description Options Description Comments Cycles per 0240 Heat Stage 1 cycles 1-12 1-12 available; typical settings: Not shown if system hour (cph) for per hour (cph)
  • Page 14 TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION Table 4. Installer Setup Menu. (Continued) Factory Setting Other Choices Installer Setup Select Number Option Description Options Description Comments Deadband 0310 2 thru 9 Heating and cooling Heating and cooling setpoints Shown only if setpoints can be set can be set no closer than 3°F...
  • Page 15 TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION Table 4. Installer Setup Menu. (Continued) Factory Setting Other Choices Installer Setup Select Number Option Description Options Description Comments Adaptive 0530 Adaptive Intelligent 0—conventional recovery — Intelligent Recovery™ control is (system starts recovery at Recovery™...
  • Page 16 TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION Table 4. Installer Setup Menu. (Continued) Factory Setting Other Choices Installer Setup Select Number Option Description Options Description Comments Temperature 0680 Standard temperature 1, 3 1—less aggressive Applies to recovery Control in control in heating.
  • Page 17: System Checkout

    TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION SYSTEM CHECKOUT Installer System Test CAUTION The Installer System Test mode is used to test the HVAC system(s). See Table 5. While in System Test mode, Equipment Damage Hazard. minimum off-time for compressors is bypassed. Minimum compressor off-time is bypassed during Installer System Test.
  • Page 18: Advanced Features

    TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION ADVANCED FEATURES Outdoor or Indoor Temperature Sensor 3. Choose Outdoor Temperature Sensor for Control Option in Installer Setup Number 0340. For accuracy, the initial reading of the indoor and outdoor 4. Choose Compressor Lockout Temperature in temperature sensors require five minutes to stabilize.
  • Page 19 TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION TROUBLESHOOTING (SEE TABLE 6) Table 6. Troubleshooting. Symptom Possible Cause Action Display does not come on. Comfort control is not being Check for 24 Vac between B and Rc. powered. Temperature settings do not The upper or lower temperature Check temperature setpoints.
  • Page 20 TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION ® U.S. Registered Trademark © 2006 American Standard Inc. American Standard Inc. All Rights Reserved Troup Highway Tyler, TX 75711-9010 Pub. No. 18-HD25D19-3 69-1790—3 M.S. Rev. 01-06...

This manual is also suitable for:

Tcont803as32daTcont802as32daTcont802as32daa

Table of Contents