Product Specifications; General Information; Overview; Installation - Trane XR103 Installation And User Manual

Non-programmable heat pump thermostat
Table of Contents

Advertisement

2.

Product Specifications

Shipping Temperature Range
Indoor Temperature Display Range
*On every application, 24VAC loads should be reviewed to be sure the indoor unit control power transformer is adequately sized.
NOTE: Use 18-gauge color-coded thermostat cable for proper wiring. Shielded cable is not typically required.
Keep this wiring at least one foot away from large inductive loads such as Electronic Air Cleaners, motors, line starters, lighting ballasts and
large distribution panels. Failure to follow these wiring practices may introduce electrical interference (noise) which can cause erratic system
operation.
All unused thermostat wire to be grounded at indoor unit chassis ground only. Shielded cable may be required if the above wiring guidelines
cannot be met. Ground only one end of the shield to the system chassis.
3.

General Information

3.1

Overview

The 103 is a non-programmable HP 2H/1C thermostat with
for use with HP applications only.
a digital display
3.2
Contents
— 1-Thermostat
— 2-Phillips slotted head mounting screws
— 2-Nylon Drywall Anchors
— 1-Installation Guide / User Guide
4.

Installation

4.1

Location

The 103 is designed for installation in climate controlled living
spaces. Place the unit in a central location with good circulation.
For proper temperature sensing, avoid exposing the 103 to heat
radiated from lamps, sun light, fireplaces or any other radiant heat
source.
Avoid locations close to windows, behind doors or alcoves with
poor air circulation, adjoining outside walls, or doors that lead to
the outside.
Select a location that prevents the 103 from being directly exposed
to air currents from supply registers or ceiling fans.
Mount the Control on a section of interior wall that does not
contain hot or cold water pipes or duct work.
Pub. No. 18HD55D1-1C-EN
SPECIFICATION
Product Models
Product
Size
Configurations
Maximum Number of Stages
Operating Temperature
Input Power (DC)
Input Power (AC)
Terminal Load
Wire Usage
System Modes
Fan Modes
09/2020
Part No. 37-7790003
DESCRIPTION
TCONT103
XR 103
3-7/8" x 5-1/2" x 1-3/16" (HxWxD)
Heat Pump
2H/1C
32°F to 105°F (0 to +41°C) / 90% RH Non Condensing
-40 to 150°F (-40 to +65°C)
Two 1.5V AAA Alkaline
20-30 VAC, NEC Class ll, 50/60 HZ
1.0A terminal/1.5A combined
18 AWG
Heating, Cooling, Off, Emergency Heat
Auto, On
45°F to 90°F
FIGURE 1. PLACEMENT OF THE 103
Correct
Placement
4.2
Mounting / Installation
Follow these steps to mount the 103 Control to the wall.
1.
Turn OFF all power to heating and cooling equipment.
2.
If an existing thermostat is being replaced:
a.
Record color and terminal marking of each wire.
b.
Disconnect the wires from the existing thermostat
being careful not to allow them to fall back into the wall.
c.
Remove the existing thermostat from the wall.
Trane XR103 Non-Programmable Thermostat
Natural heat
dissipation
from the
Thermostat
2 FEET
Optimum
Zone
Onboard
Thermistor
5 FEET
Incorre
Placem
Heat from the
within the bo
external top-dow
The onbo
by t
indo
3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tcont103

Table of Contents