Appendix B • Vission 20/20 Application Procedures
Vission 20/20 Communication Table
• All ENUM variables are of INT type
• ALL F-INT data types represent fl oating point values as INT types multiplied by 10
• All Pressures are in Psig
• All Temperatures are in Fahrenheit
• Modbus TCP addressing is PLC-style (Base 1) addressing
• On Error, Modbus TCP server only returns an error code of "Illegal Data Address"
• All registers returned (INT and F-INT) are 2-bytes long
• For Ethernet/IP, use INT data type and PLC-5 Word Range Read/Write MSG instructions
• Remote commands can't be issued if the panel is in "Remote Lock" mode
• Pulling rates should not be less then 5 sec
• Writes to the Vission should only occur when a value needs to be changed
• Lower Range & Higher Range values mentioned are default values of Vission 20/20
• Users can modify Lower Range & Higher Range values from Vission 20/20 Panel and accordingly maintain
their own table
Ethernet
Vilter
Modbus
Address
Address
IP Address
0
N50:0
40001
1
N50:1
40002
2
N50:2
40003
3
N50:3
40004
4
N50:4
40005
5
N50:5
40006
6
N50:6
40007
7
N50:7
40008
8
N50:8
40009
9
N50:9
40010
10
N50:10
40011
11
N50:11
40012
12
N50:12
40013
13
N50:13
40014
14
N50:14
40015
15
N50:15
40016
16
N51:0
40051
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0
Table B-4. Vission 20/20 Communication Table
Digital Inputs
Compressor Interlock
High Level Shutdown
Oil Level Switch #1
Oil Level Switch #2
Local / Remote
Remote Start
Remote Increase
Remote Decrease
Auxiliary 1
Auxiliary 2
Auxiliary 3
Auxiliary 4
Auxiliary 5
Auxiliary 6
Auxiliary 7
Auxiliary 8
Digital Outputs
Compressor Start
Data
Value
Type
INT
0 = OFF, 1 = ON
INT
0 = OFF, 1 = ON
INT
0 = OFF, 1 = ON
INT
0 = OFF, 1 = ON
INT
0 = OFF, 1 = ON
INT
0 = OFF, 1 = ON
INT
0 = OFF, 1 = ON
INT
0 = OFF, 1 = ON
INT
0 = OFF, 1 = ON
INT
0 = OFF, 1 = ON
INT
0 = OFF, 1 = ON
INT
0 = OFF, 1 = ON
INT
0 = OFF, 1 = ON
INT
0 = OFF, 1 = ON
INT
0 = OFF, 1 = ON
INT
0 = OFF, 1 = ON
INT
0 = OFF, 1 = ON
Lower
Higher
Mode
Range
Range
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
B - 73